Plan Review Notes For Permit 09030588 |
Permit Number |
09030588 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-06-16 14:03:28 | **DENIED*** | | | | PLANS SUBMITTED FOR PLANS REVIEW ONLY. | | | | COMMENTS TAKEN DIRECTLY FROM FIRST REVIEW. PLEASE NOTE | | THAT A RESPONSE LETTER HAS BEEN PROVIDED FOR PREVIOUS | | REVIEWS WITH EXCEPTION OF THE FIRE REVIEW. A RESPONSE | | LETTER WOULD HELP EXPEDITE THE PLAN REVIEW PROCESS AS | | COMMENT #3 WILL REQUIRE A WRITTEN RESPONSE. | | | | 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2006. PLEASE | | ADD NOTE TO CODE SUMMARY ON SHEET A-1.01. | | | | 2) PLANS SEEM TO SHOW CONFLICTING INFORMATION REGARDING | | SMOKE DETECTOR PLACEMENT. DUCT SMOKE DETECTORS SHALL BE | | PROVIDED IN THE SUPPLY DUCT IN ACCORDANCE WITH THE | | MECHANICAL CODE. IF PROJECT IS PROVIDED WITH A FIRE | | ALARM SYSTEM, DUCT SMOKE DETECTORS TO BE TIED TO THE | | ALARM SYSTEM AND INITIATE A GENERAL FIRE ALARM IN | | ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | 3) WILL THIS WORK HAVE ANY IMPACT ON EXISTING FIRE | | PROTECTION SYSTEMS? | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|