Plan Review Notes
Plan Review Notes For Permit 09030588
Permit Number 09030588
Review Stop E
Sequence Number 2
Notes
Date Text
2009-06-15 16:01:41 
  
  
 ** DENIED 2ND REVIEW *
  
 1) NOTE: AS STATED ON THE PREVIOUS REVIEW NO PERMIT
 APPLICATION HAS BEEN MADE TO DATE BY A LICENSED
 CONTRACTOR. PLEASE BE AWARE THE ELECTRICAL CODE MAY
 CHANGE ON JULY 1ST 2009.
 ALL PERMIT APPLICATIONS MUST BE APPLIED FOR PERMIT
 BEFORE THAT DATE TO REMAIN UNDER THE 2005 NEC.
  
 2) NOTE: AS STATED ON THE PREVIOUS REVIEW: NO *
 EQUIPMENT GROUNDING CONDUCTORS* ARE PERMITTED BEFORE
 THE FIRST MEANS OF DISCONNECT. THE RESPONSE FROM
 ENGINEER SPEAKS OF GROUNDING ELECTRODE CONDUCTORS. THIS
 WAS NOT THE PREVIOUS REVIEW COMMENT AND THE RISER STILL
 CLEARLY SHOWS EQUIPMENT GROUNDING CONDUCTORS BEFORE THE
 MAINS WHICH IS NOT PERMITTED.
 PLEASE SEE 250.6, 250.24.
 ** CALL IF THERE ARE ANY QUESTIONS.
  
 3) NOTE: THE PACKAGE NOW HAS A METHOD *A* FLA-COM
 SUBMITTED AS WELL AS A FORM 400C-07. PLEASE SEE FBC
 CHAPTER 13 AS ADOPTED ON MARCH 1ST 2009. THE GLITCHES
 WHICH WENT INTO EFFECT ON MARCH 1ST COMPLETELY REVISED
 CHAPTER 13. THERE IS NO MORE METHOD *C*. MAY ONLY USE
 METHOD *A* IF INCLUDING *ALL* COMPONENTS FOR THE WHOLE
 BUILDING METHOD.
 MAY NOT USE DIFFERENT METHODS PER 13-415.AB.5. BOTH A
 AND C WERE SUBMITTED BOTH OF WHICH DATED BY THE
 ENGINEER 5/22/09.
 IF USING METHOD A, ALL COMPONENTS MUST BE LISTED FOR
 WHOLE BUILDING COMPLIANCE. A CLEAR EXAMPLE IS THAT THE
 INPUT DATA REPORT ONLY INDICATES 4-50WATT FIXTURES FOR
 INTERIOR LIGHTS. THIS DOES NOT CORRELATE WITH PLANS.
 THERE ARE ALSO OTHER ITEMS SHOWN IN THE IDR WHICH ARE
 NOT PER PLANS.
 THERE ARE MORE THAN 4 FIXTURES ON PLANS ALONG WITH THE
 WATTAGE WHICH IS COMPLETELY DIFFERENT FROM THE IDR.
 ONE COPY OF FLA COM METHOD A AND ONE COPY OF FORM *C*
 IS BEING RETAINED BY THIS OFFICE ALONG WITH ONE COPY OF
 PLANS.
 4) NOTE: PLEASE LABEL NEW MAIN 6 OF 6. 230.2E
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  