2009-06-15 16:01:41 | |
| |
| |
| ** DENIED 2ND REVIEW * |
| |
| 1) NOTE: AS STATED ON THE PREVIOUS REVIEW NO PERMIT |
| APPLICATION HAS BEEN MADE TO DATE BY A LICENSED |
| CONTRACTOR. PLEASE BE AWARE THE ELECTRICAL CODE MAY |
| CHANGE ON JULY 1ST 2009. |
| ALL PERMIT APPLICATIONS MUST BE APPLIED FOR PERMIT |
| BEFORE THAT DATE TO REMAIN UNDER THE 2005 NEC. |
| |
| 2) NOTE: AS STATED ON THE PREVIOUS REVIEW: NO * |
| EQUIPMENT GROUNDING CONDUCTORS* ARE PERMITTED BEFORE |
| THE FIRST MEANS OF DISCONNECT. THE RESPONSE FROM |
| ENGINEER SPEAKS OF GROUNDING ELECTRODE CONDUCTORS. THIS |
| WAS NOT THE PREVIOUS REVIEW COMMENT AND THE RISER STILL |
| CLEARLY SHOWS EQUIPMENT GROUNDING CONDUCTORS BEFORE THE |
| MAINS WHICH IS NOT PERMITTED. |
| PLEASE SEE 250.6, 250.24. |
| ** CALL IF THERE ARE ANY QUESTIONS. |
| |
| 3) NOTE: THE PACKAGE NOW HAS A METHOD *A* FLA-COM |
| SUBMITTED AS WELL AS A FORM 400C-07. PLEASE SEE FBC |
| CHAPTER 13 AS ADOPTED ON MARCH 1ST 2009. THE GLITCHES |
| WHICH WENT INTO EFFECT ON MARCH 1ST COMPLETELY REVISED |
| CHAPTER 13. THERE IS NO MORE METHOD *C*. MAY ONLY USE |
| METHOD *A* IF INCLUDING *ALL* COMPONENTS FOR THE WHOLE |
| BUILDING METHOD. |
| MAY NOT USE DIFFERENT METHODS PER 13-415.AB.5. BOTH A |
| AND C WERE SUBMITTED BOTH OF WHICH DATED BY THE |
| ENGINEER 5/22/09. |
| IF USING METHOD A, ALL COMPONENTS MUST BE LISTED FOR |
| WHOLE BUILDING COMPLIANCE. A CLEAR EXAMPLE IS THAT THE |
| INPUT DATA REPORT ONLY INDICATES 4-50WATT FIXTURES FOR |
| INTERIOR LIGHTS. THIS DOES NOT CORRELATE WITH PLANS. |
| THERE ARE ALSO OTHER ITEMS SHOWN IN THE IDR WHICH ARE |
| NOT PER PLANS. |
| THERE ARE MORE THAN 4 FIXTURES ON PLANS ALONG WITH THE |
| WATTAGE WHICH IS COMPLETELY DIFFERENT FROM THE IDR. |
| ONE COPY OF FLA COM METHOD A AND ONE COPY OF FORM *C* |
| IS BEING RETAINED BY THIS OFFICE ALONG WITH ONE COPY OF |
| PLANS. |
| 4) NOTE: PLEASE LABEL NEW MAIN 6 OF 6. 230.2E |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |