Plan Review Notes
Plan Review Notes For Permit 09030588
Permit Number 09030588
Review Stop M
Sequence Number 1
Notes
Date Text
2009-04-14 16:15:22REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: PLANS SUBMITTED FOR PLANS REVIEW ONLY. NO PERMIT
 APPLICATION SUBMITTED AT THIS TIME.
  
 1. PAGE M-3: EXHAUST FAN SCHEDULE CALLS FOR EF-1 AND
 EF-2 WHILE PAGE M-3 SHOWS EF-4 AND EF-5. PLEASE
 COORIDINATE PLANS AND EQUIPMENT SCHEDULES.
  
 2. PAGE M-3: MECHANICAL NOTES 15, 16 AND 18 REFERENCE
 THE 2004 FBC. PLEASE UPDATE ALL CODES TO REFERENCE THE
 2007 FBC, WHICH IS IN EFFECT AS OF MARCH 1, 2009.
  
 3. PAGE M-4: DIFFUSER DETAIL SHOWS FLEX DUCT SUPPORTED
 BY 1 INCH BAND. ALL SUPPORTS FOR FLEX DUCT SHALL BE
 MIN. 1 1/2" WIDE MINIMUM PER FBC-M 603.5.6.6.
  
 4. PAGE M-4: ROOF CURB DETAILS SHOW ATTACHMENT BASED ON
 ROOF JOIST AND METAL DECK CONSTRUCTION. ARCHITECTURAL
 PLANS INDICATE THIS BUILDING ROOF STRUCTURE IS CONCRETE
 DECK/PLANKS. PLEASE PROVIDE CURB INSTALLATION DETAIL
 APPROPRIATE FOR THE EXISTING CONSTRUCTION, DESIGNED FOR
 WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12.
  
 5. PAGE M-4 AND E-1.01: THESE PAGES SHOW DUCT SMOKE
 DETECTOR INSTALLED IN THE RETURN DUCT WHILE PAGE M-1
 SHOWS THE DUCT SMOKE DETECTOR INSTALLED IN THE SUPPLY
 DUCT. PLEASE COORDINATE PLANS AND DETAILS, SHOWING THE
 DUCT SMOKE DETECTOR BEING INSTALLED IN THE SUPPLY DUCT
 IN ACCORDANCE WITH FBC-M 606.2.1.
  
 6. PROVIDE MANUFACTURER'S DATA FOR THE PROPOSED RTU
 SHOWING IT IS DESIGNED FOR WIND RESOSTANCE. MECHANICAL
 APPLIANCES EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M
 301.12.
  
 7. ON DOWN-FLOW UNITS (SUCH AS THE PROPOSED RTU), A
 WATER-LEVEL MONITORING DEVICE SHALL BE INSTALLED INSIDE
 THE PRIMARY DRAIN PAN IN ACCORDANCE WITH FBC-M
 307.2.3.1. THIS DEVICE SHALL SHUT OFF THE EQUIPMENT
 SERVED IN THE EVENT THAT THE PRIMARY DRAIN BECOMES
 RESTRICTED. EXTERNALLY INSTALLED DEVICES AND DEVICES
 INSTALLED IN THE DRAIN LINE SHALL NOT BE PERMITTED.
  
 NOTE: MECHANICAL PLANS WERE NOT SIGNED AND SEALED BY
 THE ENGINEER. ONCE PLANS ARE SUBMITTED FOR PERMIT,
 PLANS SHALL BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL IN ACCORDANCE WITH FS 471 AND FAC RULE
 61G15-23.002.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]