2009-04-16 08:42:57** DENIED**
  
  
  
 1) NOTE: PLEASE SEE NEC 250.6 AND 250 AS RISER SHOWS AN
 EQUIPMENT GROUNDING CONDUCTOR BEFORE THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED. THIS 3/0 CONDUCTOR
 WOULD CREATE OBJECTIONABLE CURRENTS.
  
 2) NOTE: PLEASE PROVIDE LOCATION OF METERING EQUIPMENT.
 PLEASE SEE FPL MINIMUM SERVICE STANDARDS. IF EXISTING
 PLEASE SHOW.
  
 3) NOTE: PLANS SUBMITTED FOR PLAN REVIEW ONLY AND HAVE
 NOT BEEN SUBMITTED FOR PERMIT BY A LICENSED CONTRACTOR.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  