2009-04-06 13:53:40PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2007 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 FBC R4101.6 ENGINEERING DESIGN.
 DESIGN SHALL BE IN CONFORMITY WITH ANSI/NSPI 7 FOR
 ENTRAPMENT AVOIDANCE.
  
 NOTES:
 CALCULATIONS SHOWING TDH, PUMP HORSEPOWER, AND MAXIMUM
 FLOW RATES FOR MAINDRAIN BRANCH AND MAIN PIPING (
 VELOCITY FOR MAINDRAIN BRANCH PIPING IS 6 FEET PER
 SECOND MAXIMUM WHEN ONE OF A PAIR IS BLOCKED. ETC.)
  
 LISTED SUCTION OUTLETS ARE REQUIRED TO MEET ASME/ANSI
 A112.19.8 MOST RECENT EDITION.
  