Plan Review Notes
Plan Review Notes For Permit 09030474
Permit Number 09030474
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-03 16:23:10** DENIED **
  
  
 1) NOTE: PLANS SUBMITTED AFTER MARCH 1ST, 2009 SHALL
 ALL BE UNDER THE LATEST ADOPTED FLORIDA BUILDING CODES
 PER FS 553.73
 CURRENTLY 2007 FBEC W/ 2007 REVISIONS.
  
 2) NOTE: PLEASE COORDINATE ALL ELECTRICAL DEVICES,
 DETAILS ETC FOE ACTUAL EQUIPMENT SPECIFIC TO THIS
 LOCATION AND PROPOSED POOL. SOME DETAILS INCLUDE SPA
 ETC YET SOME OTHER AREAS OF PLANS HAVE DELETED SOME OF
 THESE ITEMS.
 NEC 2005 220, 680, 310.163, 240.4 GIVEN AS GENERAL AS
 IT IS NOT KNOWN WHICH IS TO BE REVIEW
 FBC 106.1.1 FOR CLARITY AND COORDINATION OF RECORD
 PLANS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  