Plan Review Notes
Plan Review Notes For Permit 09030385
Permit Number 09030385
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-01 14:27:13** DENIED REVIEW **
  
 1) NOTE: ALL PLANS WHEN MEETING EXEMPTIONS IN FS
 471.003 AND 481.229 SHALL CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE DESIGNER MEETING EXEMPTIONS.
  
 2) NOTE: PLEASE SHOW MINIMUM COMPLIANCE WITH FBC
 13-415.AB.1.1, .1.2, .1.3.
 THIS IS A BUILDING GREATER THAN 5K SQ FT. ALL NEW
 LIGHTING CONTROLS MUST MEET THE ABOVE.
  
 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.AB.5, 13-415.B.1.
  
 4) NOTE: PLEASE BE SURE TO PROVIDE DESIGNATIONS,
 CIRCUITING FOR NEW ITEMS TO A PANEL SCHEDULE.
 240.4.310.16, 408.4 SIZE OF CIRCUITS, CONDUCTORS OVER
 CURRENT PROTECTION.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  