Plan Review Notes
Plan Review Notes For Permit 09030378
Permit Number 09030378
Review Stop ENG
Sequence Number 2
Notes
Date Text
2009-08-04 11:02:49FAILED
  
 WIND LOAD CALCULATIONS RECEIVED. HOWEVER, 3 OF THE 4
 PREVIOUS REQUESTS FROM 04-10-09 OF THE LAST ENGINEERING
 SERVICES REVIEW ARE STILL OUTSTANDING AS NOTED:
  
 #1 PROVIDE STANDARD DETAIL TO SHOW MINIMUM POLE
 INSTALLATIONS TO EXISTING UTILITIES AND FIRE HYDRANTS
 (5 FEET MINIMUM)
  
 #2 MINIMUM A.D.A. ACCESSIBILITY DISTANCE REQUIREMENTS
 BETWEEEN LIGHT POLE INSTALLATIONS
  
 #4 SHOW NORTH ARROW ON PLANS
  
 ITEMS 1 AND 2 COULD BE ADDRESSED BY THE ADDITION OF
 THIS INFORMATION TO SHEET E-13.
  
 ITEM 4 COULD BE ADDRESSED WITH THE ADDITION OF THE
 NORTH ARROW SHOWN ON A COVER SHEET.
  
 THIS WOULD HELP FACILITATE APPROVAL OF THESE PLANS BY
 THIS DEPARTMENT IN AN EXPEDITIOUS MANNER.
  
 PLEASE CONTACT THE PLANNER WITH ANY QUESTIONS OR
 COMMENTS:
  