2009-08-17 11:57:35 | |
| ** DENIED REVIEW ** |
| |
| SAME NOTES AS PREVIOUS REVIEW: |
| |
| 1) NOTE: EACH METER/SERVICE POINT NEEDS TO HAVE AN |
| ADDRESS AND PERMIT APPLICATION FOR EACH LOCATION. |
| |
| ** PREVIOUS NOTES ** |
| THE APPLIED LOCATIONS AND SCOPE OF WORK ON PERMIT |
| APPLICATION DO NOT CORRELATE. |
| THE APPLIED LOCATION IS FOR EDMOR RD, HOWEVER PLANS |
| SUBMITTED INCLUDE GEORGIA AVE, NOTTINGHAM BLVD. WHICH |
| IS NOT CLOSE, ON SAME GRID OR AREA OR METER. |
| BASED ON THE SCOPE OF WORK SUBMITTED ON PLANS THERE |
| WOULD BE SEPARATE PERMIT APPLICATIONS AS LIGHTING IS |
| BEING FED FROM MORE THAN ONE SERVICE POINT. THE FACT IS |
| THERE IS NO SERVICE POINT LOCATION SHOWN. |
| ** PLEASE SUBMIT PLANS ONLY FOR SCOPE OF WORK BEING |
| APPLIED FOR. |
| |
| 2) NOTE: THIS VALUE WAS NOT INCREASED ON APPLICATION. |
| THE VALUE FOR EACH PHASE/PERMIT/SERVICE POINT MAY BE |
| BROKEN DOWN. |
| THE APPLIED VALUATION CAN NOT BE DETERMINED BASED ON |
| THE PLANS SUBMITTED, THE AMOUNT OF WORK SHOWN COMPARED |
| TO THE ACTUAL SCOPE SHOWN. |
| VALUE MUST INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, |
| DESIGN COSTS EVEN IF ANY OF THESE ITEMS ARE OWNER |
| SUPPLIED. |
| FBC 108.3 |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |