2009-04-02 17:04:12** DENIED REVIEW **
  
 1) NOTE: PLEASE KNOW THAT PER FS 553.73: THE STATE OF
 FLORIDA AS OF MARCH 31ST,2009 HAS ADOPTED THE 2007 FBC
 WITH 2009 GLITCH AMENDMENTS.
 THE PLANS SUBMITTED ARE UNDER 2004 FBC.
 PLEASE ALSO SEE THE ELECTRICAL CODE REFERENCE ON PLANS
 FOR GROUNDING IS FROM THE 1996 NEC.
 THE CURRENT SECTION UNDER THE 2005 NEC IS NOT 250.95
 FOR EQUIPMENT GROUNDING CONDUCTORS.
  
 2) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE LED
 LIGHTING SHOWN FOR SIGN. THERE IS NO INFORMATION ON THE
 DRIVER OR VOLTAGE WHICH DRIVES THESE LIGHTS.
 NO DISCONNECT SWITCH SHOWN.
 600.7,600.6,600.5,250.122, ETC
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  