Plan Review Notes For Permit 09030353 |
Permit Number |
09030353 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-05-06 13:01:01 | REDLINED PLANS. THE THIRD SMALL APPLIANCE CIRCUIT WAS | | NOT FIGURED INTO LOAD CALCULATIONS AS STATED IN | | PREVIOUS REVIEW COMMENTS AND 220.52/53 OF THE NEC. THIS | | WILL NOT AFFECT THE SERVICE SIZE. PLEASE REVISE WITH | | CORRECTION IF THERE ARE ANY OTHER REVISIONS BEFORE | | ROUGH. |
|