2009-04-10 13:08:46 | * DENIED** |
| |
| 1) NOTE: RISER INDICATES THE METER CAN AT 200AMPS |
| HOWEVER THIS IS NOT RATED FOR THE SERVICE SIZE AS |
| SHOWN. |
| 110.3 90.7 |
| |
| 2) NOTE: PLEASE SEE SMOKE ALARM WHICH NEEDS TO BE |
| LOCATED INSIDE BEDROOM. THIS WOULD HAVE BEEN REDLINED |
| IF IT WAS THE ONLY ITEM. NFPA-72 11.5.1. |
| |
| 3) NOTE: PLEASE SEE 422.13 AS THE LOAD FOR THE WATER |
| HEATER NEEDS TO BE SHOWN AT 125%. NEW IN 2005 NEC AS OF |
| DECEMBER 2006. |
| |
| 4) NOTE: PLEASE SEE WATER HEATER IS SHOWN WITH A |
| RECEPTACLE WITH CORD AND PLUG CONNECTION WHICH IS NOT |
| PERMITTED. 422.30, 422.31 |
| MUST BE A DISCONNECT. |
| ** STORAGE TYPE WATER HEATER ALSO SHOWN AS BEING |
| OUTSIDE WHICH MUST BE LISTED TO BE LOCATED OUTSIDE. |
| |
| 5) NOTE: MISSING REQUIRED DISCONNECT FOR CONDENSING |
| UNIT. 440.11 |
| |
| 6) NOTE: MISSING WP GFI FOR CONDENSING UNIT PER 210.63, |
| 210.8A |
| |
| 7) NOTE: PLEASE SEE PANEL SCHEDULE WHICH INDICATES A |
| CIRCUIT FOR SMALL APPLIANCE #13 HOWEVER NO #13 IS ON |
| PLANS. |
| CIRCUIT #17 IS ALSO FEEDING MULTIPLE AREAS WHICH PER |
| 210.11B1 IS REQUIRED TO BE ON ONE OR MORE OF THE SMALL |
| APPLIANCE CIRCUITS. THE KITCHEN, DINING ROOM ETC ALSO |
| FEEDS LIVING ROOM, LIGHTS ETC./ |
| PLEASE SEE 210.52B1, 210.11C1, AND 220.53 FOR THE LOADS |
| WHICH ARE REQUIRED TO BE FIGURED. |
| |
| 8) NOTE: ALL AIC RATINGS MUST BE STATED ON PLANS. |
| PLEASE KEEP IN MIND MANY OF THE FPL TRANSFORMERS ARE |
| BEING UPDATED WHICH MAY HAVE A HIGHER AVAILABLE FAULT |
| CURRENT. PLEASE BE SURE TO CHECK WITH THE LOCAL FPL |
| REPRESENTATIVE. |
| |
| 9) NOTE: PLEASE COORDINATE RISER AND PANELS. PANEL |
| SCHEDULE FOR MAIN HOUSE IS LISTED AS 150AMP MCB YET |
| RISER SHOWS COMPLETELY DIFFERENT EQUIPMENT. |
| 230.70, 230.71, 110.3 SECTIONS GIVEN AS GENERAL |
| SECTIONS DUE TO MORE COORDINATION OF PLANS. |
| FBC 106.1.1 FOR CLARITY. |
| |
| 10) NOTE: PLEASE PROVIDE A RESPONSE FOR SCOPE OF WORK |
| AT GUEST HOUSE/ COTTAGE. WILL THE NEW ELECTRICAL |
| SERVICE BE THE ONLY WORK? |
| |
| 11) NOTE: PLANS DO NOT INDICATE LOAD CALCULATIONS FOR |
| SERVICE. PLEASE SEE NEC 220 |
| ONLY SHOWS LOAD FOR MAIN HOUSE. |
| |
| |
| |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |