Plan Review Notes
Plan Review Notes For Permit 09030353
Permit Number 09030353
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-10 13:08:46* DENIED**
  
 1) NOTE: RISER INDICATES THE METER CAN AT 200AMPS
 HOWEVER THIS IS NOT RATED FOR THE SERVICE SIZE AS
 SHOWN.
 110.3 90.7
  
 2) NOTE: PLEASE SEE SMOKE ALARM WHICH NEEDS TO BE
 LOCATED INSIDE BEDROOM. THIS WOULD HAVE BEEN REDLINED
 IF IT WAS THE ONLY ITEM. NFPA-72 11.5.1.
  
 3) NOTE: PLEASE SEE 422.13 AS THE LOAD FOR THE WATER
 HEATER NEEDS TO BE SHOWN AT 125%. NEW IN 2005 NEC AS OF
 DECEMBER 2006.
  
 4) NOTE: PLEASE SEE WATER HEATER IS SHOWN WITH A
 RECEPTACLE WITH CORD AND PLUG CONNECTION WHICH IS NOT
 PERMITTED. 422.30, 422.31
 MUST BE A DISCONNECT.
 ** STORAGE TYPE WATER HEATER ALSO SHOWN AS BEING
 OUTSIDE WHICH MUST BE LISTED TO BE LOCATED OUTSIDE.
  
 5) NOTE: MISSING REQUIRED DISCONNECT FOR CONDENSING
 UNIT. 440.11
  
 6) NOTE: MISSING WP GFI FOR CONDENSING UNIT PER 210.63,
 210.8A
  
 7) NOTE: PLEASE SEE PANEL SCHEDULE WHICH INDICATES A
 CIRCUIT FOR SMALL APPLIANCE #13 HOWEVER NO #13 IS ON
 PLANS.
 CIRCUIT #17 IS ALSO FEEDING MULTIPLE AREAS WHICH PER
 210.11B1 IS REQUIRED TO BE ON ONE OR MORE OF THE SMALL
 APPLIANCE CIRCUITS. THE KITCHEN, DINING ROOM ETC ALSO
 FEEDS LIVING ROOM, LIGHTS ETC./
 PLEASE SEE 210.52B1, 210.11C1, AND 220.53 FOR THE LOADS
 WHICH ARE REQUIRED TO BE FIGURED.
  
 8) NOTE: ALL AIC RATINGS MUST BE STATED ON PLANS.
 PLEASE KEEP IN MIND MANY OF THE FPL TRANSFORMERS ARE
 BEING UPDATED WHICH MAY HAVE A HIGHER AVAILABLE FAULT
 CURRENT. PLEASE BE SURE TO CHECK WITH THE LOCAL FPL
 REPRESENTATIVE.
  
 9) NOTE: PLEASE COORDINATE RISER AND PANELS. PANEL
 SCHEDULE FOR MAIN HOUSE IS LISTED AS 150AMP MCB YET
 RISER SHOWS COMPLETELY DIFFERENT EQUIPMENT.
 230.70, 230.71, 110.3 SECTIONS GIVEN AS GENERAL
 SECTIONS DUE TO MORE COORDINATION OF PLANS.
 FBC 106.1.1 FOR CLARITY.
  
 10) NOTE: PLEASE PROVIDE A RESPONSE FOR SCOPE OF WORK
 AT GUEST HOUSE/ COTTAGE. WILL THE NEW ELECTRICAL
 SERVICE BE THE ONLY WORK?
  
 11) NOTE: PLANS DO NOT INDICATE LOAD CALCULATIONS FOR
 SERVICE. PLEASE SEE NEC 220
 ONLY SHOWS LOAD FOR MAIN HOUSE.
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved