Date |
Text |
2009-04-14 11:07:18 | 2007 FBC |
| LEVEL 3 ALTERATION |
| |
| DENIED BY BUILDING |
| |
| NOTE: A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| WILL BE REQUIRED. FS 713 |
| |
| 1) SPECIFY THE LEVEL OF ALTERATION FOR THE PROPOSED |
| WORK ON SHEET 1.2. SEE LEVEL 3 ALTERATION IN THE 2007 |
| FBC EXISTING BUILDING. FBC EB SECTION 401.4. |
| |
| 2) UPDATE THE EDITION OF ASCE 7 -02 SPECIFIED ON SHEET |
| 1.2 TO CORRESPOND TO THE 2007 FBC WHICH REFERENCES ASCE |
| 7-05. |
| |
| 3) ON 1.2 UNDER CODES FOR REFERENCE, PLEASE UPDATE 2004 |
| FBC W/2006 REVISIONS TO 2007 FBC. |
| |
| 4) OM THE FOUNDATION PLAN ON SHEET 2.2 REFERENCES ARE |
| MADE TO DETAILS ON DRAWING 2.1. THERE IS NO DRAWING |
| SHEET 2.1, THESE DETAILS ARE LOCATED ON SHEET 2.2. |
| PLEASE CORRECT. |
| |
| 5) SECTION C ON 2.2 FOR THE 4" X 4" WOOD COLUMN AT THE |
| FRONT PORCH DOES NOT SPECIFY THE CONNECTOR FOR THE BASE |
| OF THE COLUMN. THE NOTE IS FOR ATTACHING A WOOD FRAME |
| WALL. PLEASE CORRECT. |
| |
| 6) THE ROOF SHEATHING FASTENING THAT IS SPECIFIED ON |
| SHEET 2.2 IS INCORRECT. FBC R803.2.3.1 REQUIRES 8D RING |
| SHANK NAILS AT 6" OC AT EDGES AND INTERMEDIATE FRAMING |
| IN ROOF ZONES 1 AND 2 AND 4" OC IN ZONE 3. PLEASE |
| REVISE. |
| |
| 7) ENERGY CALCULATION FORM 600 C-04R WAS SUBMITTED FOR |
| 539-1/2 21ST STREET. THE PERMIT APPLICATION IS ONLY FOR |
| THE MAIN HOUSE AND DOES NOT MENTION THE OTHER |
| STRUCTURE. PLEASE REMOVE THIS FORM. NOTE: THE 2008 |
| VERSION OF THE FORM IS REQUIRED BY THE 2007 FBC. |
| |
| 8) PLEASE SUBMIT THE 2008 ENERGY CALCULATION FORMS AS |
| REQUIRED BY 2007 FBC GLITCH AMENDMENTS R N1100.3. |
| |
| 9) UPDATE THE STATE PRODUCT APPROVALS TO THE 2007 CODE |
| VERSIONS. DCA RULE 9B-72. |
| |
| 10) SUBMIT TWO (2) CLEAR COPIES OF THE JELD WEN |
| OUTSWING DOOR PRODUCT APPROVALS. DCA RULE 9B-72 AND FBC |
| 106.1* CITY AMENDMENTS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |