2009-03-30 10:14:17 | BUILDING PLAN REVIEW |
| PERMIT: 09030347 |
| ADD: 360 COLUMBIA DRIVE |
| CONT: SISCA CONSTRUCTION SERVICES LLC |
| TEL: (561)686-5545 |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 3) PROVIDE A DOOR AND WINDOW SCHEDULE WITH THE OPENING |
| SIZE OF EACH DOOR AND WINDOW. SHOW THE DIMENSION OF THE |
| STOREFRONTS GLASS WITH THE LOCATION OF THE INTERMEDIATE |
| HORIZONTAL MULLION. |
| |
| 4) NO PRODUCT APPROVAL FOR THE WINDOWS AND MULLIONS |
| WERE SUBMITTED. FROM THE PRODUCT APPROVALS INDICATE |
| WHICH SYSTEM SHALL BE USED INCLUDING THE TYPE OF DOOR |
| (DOUBLE OR SINGLE) GLASS TYPE PER THE TABLES GIVEN, THE |
| TYPE OF MULLION ETC. SHOW THE STRUCTURAL ATTATCHMENT |
| DETAIL FOR THE STOREFRONT. ADDITIONAL INFORMATION IS |
| REQUIRED 106.1.2* |
| |
| 5) THE CLAIMED VALUATION ON THE APPLICATION SEEMS LOW |
| FOR THE SCOPE OF WORK SHOWN. THE VALUE SHALL BE THE |
| TOTAL REPLACEMENT COST EXCLUDING LAND VALUE. A FAIR |
| MARKET VALUE SHALL BE STATED ON THE APPLICATION OR WE |
| MAY DO A VALUATION USING MARSHALL-SWIFT AND MEANS COST |
| ANALYSIS SERVICES PER 108.3* |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| PHONE (561)805-6726 |
| FAX (561) 806-6676 |