Plan Review Notes For Permit 09030300 |
Permit Number |
09030300 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-03-31 15:44:44 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | FROM PREVIOUS LIST: | | | | 2. ON EITHER A FLOOR PLAN OR ELEVATIONS, SHOW LOCATION | | AND SCOPE OF REPAIR AREA(S). NOTE WHICH REPAIR DETAIL | | WILL BE USED IN EACH LOCATION. RATED AND UNRATED WALL | | SECTIONS WERE SUBMITTED. ON EITHER FLOOR PLANS OR | | ELEVATIONS SHOW ALL RATED WALLS WHICH WILL BE REPAIRED. | | FBC 6 AND FBC 7. | | | | PARTIALLY ADDRESSED. FLOOR PLAN/ELEVATION SUBMITTED, | | AREA OF WORK MARKED, BUT NOT CLEAR WHY PATIO/BALCONETTE | | DETAIL WAS SUBMITTED; DOES WORK AREA EXTEND INTO THE | | PATIO AREA? WHY DOESN'T THE PATIO WALL HAVE THE SAME | | FIRE RESISTANCE RATING AS THE OTHER EXTERIOR WALL? FBC | | CHAPTERS 5, 6, 7. | | | | 4. PLEASE PROVIDE LEGIBLE DETAILS. FOR INSTANCE, DETAIL | | MARKED 6 AD77, WINDOW HEAD DETAIL. | | | | DETAILS NOT LEGIBLE. THIS PERMIT CAN BE ISSUED WITH | | PROVISO, AT OWNER'S/CONTRACTOR'S RISK; SUBJECT TO FIELD | | INSPECTOR'S DISCRETION, REVISION CLARIFYING DETAILS MAY | | BE REQUIRED. | | |
|