2009-03-31 15:44:44****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 2. ON EITHER A FLOOR PLAN OR ELEVATIONS, SHOW LOCATION
 AND SCOPE OF REPAIR AREA(S). NOTE WHICH REPAIR DETAIL
 WILL BE USED IN EACH LOCATION. RATED AND UNRATED WALL
 SECTIONS WERE SUBMITTED. ON EITHER FLOOR PLANS OR
 ELEVATIONS SHOW ALL RATED WALLS WHICH WILL BE REPAIRED.
 FBC 6 AND FBC 7.
  
 PARTIALLY ADDRESSED. FLOOR PLAN/ELEVATION SUBMITTED,
 AREA OF WORK MARKED, BUT NOT CLEAR WHY PATIO/BALCONETTE
 DETAIL WAS SUBMITTED; DOES WORK AREA EXTEND INTO THE
 PATIO AREA? WHY DOESN'T THE PATIO WALL HAVE THE SAME
 FIRE RESISTANCE RATING AS THE OTHER EXTERIOR WALL? FBC
 CHAPTERS 5, 6, 7.
  
 4. PLEASE PROVIDE LEGIBLE DETAILS. FOR INSTANCE, DETAIL
 MARKED 6 AD77, WINDOW HEAD DETAIL.
  
 DETAILS NOT LEGIBLE. THIS PERMIT CAN BE ISSUED WITH
 PROVISO, AT OWNER'S/CONTRACTOR'S RISK; SUBJECT TO FIELD
 INSPECTOR'S DISCRETION, REVISION CLARIFYING DETAILS MAY
 BE REQUIRED.
  