Plan Review Notes
Plan Review Notes For Permit 09030267
Permit Number 09030267
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-01 14:07:16 
  
 ** DENIED REVIEW **
  
 ** PLANS ARE FOR FINAL *CO*> ALL ITEMS NEED TO BE
 CORRECT AND SPECIFIC FOR FINAL RECORD SET OF PLANS.
  
  
  
 1) NOTE: PLANS STATE THERE IS A NEW DESIGNER OF RECORD.
 PER FS 471.003 WHEN MEETING THE EXCEPTIONS FOR LICENSED
 DESIGNER PER FS 489, THE DESIGNER SHALL TAKE
 RESPONSIBILITY OF SAID PLANS BY PRINTING NAME AND
 SIGNING SAID PLANS.
  
 2) NOTE: PLEASE COORDINATE RISER AND PANEL. RISER
 STATES PANEL IS A MCB YET PANEL STATES THIS AS A MAIN
 LUG ONLY PANEL.
 230.70,230.71
 FBC 106.1.1,106.5 FOR CLARITY AND COORDINATION OF FINAL
 RECORD PLANS.
  
 3) NOTE: PLEASE COORDINATE AND COMPLETE PANEL SCHEDULE.
 ALL ITEMS LISTED ON PANEL SCHEDULE SHALL BE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED.
 THIS ALSO MEANS WHEN PLANS ARE ON-SITE FOR FINAL
 INSPECTION THE PANEL SCHEDULE ON PLANS SHOULD MATCH THE
 LOCATION PANEL SCHEDULE. THIS WAS GONE OVER PREVIOUSLY.
 PLEASE SEE THE FOLLOWING TEXT FROM THE 408.4. WHICH
 STATES THE USE OF *GENERAL LIGHTING OR GENERAL
 RECEPTACLES* IS NOT ACCEPTABLE.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
  
 4) NOTE: PLEASE SEE DRYER LISTED ON PLANS CIRCUITED TO
 CIRCUIT 17 AND 18. THIS IS NOT POSSIBLE AS BOTH OF
 THESE ARE ON THE SAME PHASE. THIS SEEMS TO BE SOME SORT
 OF MISPRINT. AS NOTED ABOVE IN COMMENT #3 PLEASE
 REVISE.
 PLEASE ALSO SEE PANEL SCHEDULE WHICH STATES *EXTERIOR
 LIGHT* AS CIRCUIT #25. HOWEVER NOT CIRCUIT #25 ON
 PLANS.
  
 5) NOTE: PANEL SCHEDULE STATES *ALL CIRCUITING IN THE
 HOUSE* IS TO BE PLACED IN CONDUIT. IS THIS THE CASE? IS
 THE ENTIRE HOUSE ALL IN CONDUIT SIZED PER PANEL
 SCHEDULE SUBMITTED?
 ( THIS IS MOST LIKELY NOT THE CASE, PLEASE
 ADJUST/REVISE PANEL SCHEDULE.
  
 6) NOTE: RISER STATES 22K AIC RATED MAINS, YET PANEL
 SCHEDULE STATES 10K. IS THE 10K AIC RATING FOR BRANCH
 BREAKERS?
 110.9
  
 7) NOTE: PLEASE SEE PANEL SCHEDULE WHICH INDICATES #15
 AWG FOR BATH CIRCUIT #9. THERE IS NO #15 AWG AND
 MINIMUM MUST BE PER 310.16,210.11C3.
  
 8) NOTE: ORIGINAL PLANS CALLED FOR COLD WATER PIPE AS
 PART OF THE GROUNDING ELECTRODE SYSTEM. NO CWP IS SHOWN
 ON RISER ANYMORE, IS THERE CWP NO LONGER METALLIC?
 250.50,250104 ETC.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  