Plan Review Notes
Plan Review Notes For Permit 09030254
Permit Number 09030254
Review Stop E
Sequence Number 5
Notes
Date Text
2009-11-06 09:58:46REVISION REQUIRED
  
 1} CLARIFY SHADED AREA IN FRONT OF PANEL APARTMENT #1,
 SHEET E1 110.26.
  
 2} PANEL IN MECH. ROOM NOT SHOWN ON RISER, SHEET E3.
 215.5.
  
 3} #6 GROUND IN THE RISER IS IN VIOLATION OF 250.6,
 250.24(A) & (A)(1). MUST BE REMOVED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  