 APPLICATION #09030254 ELECTRICAL PLAN REVIEW
 310 CORDOVA ROAD 10/27/09
 WEST PALM BEACH, FL.
  
 REVISION DENIED
  
 1} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3).
 CORRELATE WITH MECHANICAL PLAN, SHEET M1. NOTE THE NEW
 AIR HANDLER LOCATION ON SHEET M1 OF THIS PLAN DOES NOT
 CORRELATE TO THE LOCATION OF THE PERMIT SET SHEET E1
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 THE LOCATION MUST BE ON THE REVISION. THE PERMIT SET OF
 PLANS INDICATES PANELS "M" & "H" PANEL SCHEDULES BUT
 ONLY ONE PANEL SHOWN ON THE FLOOR PLAN IN THE MAIN
 HOUSE. NOTE: THE REVISION SUBMITTED ON SEPTEMBER 3RD
 DID NOT HAVE THE PANELS LABELED ON THE RISER SHEET E3
  
 3} SUBMIT REVISED SHEET E3 WITH REVISED LOAD
 CALCULATIONS AND PANEL SCHEDULES TO SHOW ADDED (OR
 EXISTING) LOADS, WALL HEATERS, TANKLESS WATER
 HEATERS(NOT SHOWN ON REVISED PLUMBING PLAN) TREADMILL,
 SPACE HEATER WINDOW A/C (DEDICATED) CIRCUITS, ETC.
  
 4} THE PANEL LOCATION IN THE APARTMENT ON SHEET E1 IS
 EITHER IN VIOLATION OF 240.24(E) BATHROOMS OR 110.26 IF
 FACING STUDIO 1, DEPENDING ON WHAT THE SHADED AREA IN
 THE STUDIO REPRESENTS, LABEL SAME FOR CLARIFICATION.
  
 5} KITCHEN RECEPTACLE MUST COMPLY WITH 210.8(A)(6) GFI,
 ALL UNITS. THE ONLY ONES LABLED ARE IN THE MAIN HOUSE @
 THE SINK. LABEL ALL.
  
 6} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). SEE BATH #3 SHEET E2
 APARTMENT.
  
 7} 210.8(A)(3) DWELLING UNITS ALL 125-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES INSTALLED
 IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) SHALL
 HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL OUTDOORS.*** LABEL ALL, SEE E1 1ST FLOOR
 PLAN.
  
 8} THE LOCATION OF THE TANKLESS WATER HEATER LOCATED IN
 THE STORAGE ROOM, SHEET E1, IS IN VIOLATION OF 110.26
 SPACING REQUIREMENTS IF LOCATED WHERE THE
 ???RECEPTACLE??? IS SHOWN. SEE 240.24(D) IF AN
 OVERCURRENT DEVICE IS TO BE INSTALLED IN THE STORAGE
 ROOM.
  
 NOTE: THE #6 GROUND SHOWN INSTALLED WITH THE
 SERVICE-ENTRANCE CONDUCTORS, SHEET E3, MUST NOT BE
 INSTALLED AND IS A VIOLATION OF 250.6 AND SHALL BE
 INSTALLED PER 250.24(A) & (A)(1).
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITING
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  