2009-05-07 12:01:03 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. PLEASE UPDATE CODE REFERENCES ON PLAN TO REFLECT NEW |
| CODES IN EFFECT AT TIME OF PERMIT APPLICATION. THE 2007 |
| FLORIDA BUILDING CODE WITH 2009 SUPPLEMENT IS IN EFFECT |
| AS OF MARCH 1, 2009. |
| |
| 2. PAGE M1 SHOWS A NEW AIR CONDITIONING SPLIT SYSTEM |
| BEING ADDED TO HOUSE. ELECTRICAL PLANS MAKE NO |
| PROVISIONS FOR THIS NEW A/C SYSTEM AT THE AIR HANDLER |
| OR CONDENSING UNIT LOCATIONS. ALSO, THE NEW SYSTEM IS |
| NOT ACCOUNTED FOR ON THE ELECTRICAL PANEL SCHEDULE. |
| PLEASE SHOW PROPER CIRCUITING AND OVERCURRENT |
| PROTECTION IN ACCORDANCE WITH FBC-R M1401.1. |
| |
| 3. THE AREA BEING SERVED BY THE ABOVE SYSTEM IS A |
| PREVIOUSLY UNCONDITIONED SPACE. ANY INCREASE IN THE |
| CONDITIONED AREA IS DEFINED AS AN ADDITION IN FBC-R |
| SECTION N1100.7.3. ADDITIONS TO EXISTING RESIDENTIAL |
| BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION |
| AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD |
| A OR B AS APPLICABLE IN ACCORDANCE WITH FBC-R SECTION |
| N1100.0.3. ADDITIONS THAT ARE UNABLE TO COMPLY WITH |
| CODE REQUIREMENTS FOR THE ADDITION ALONE MAY COMPLY |
| WITH THE CODE BY BRINGING THE ENTIRE BUILDING INTO |
| COMPLIANCE WITH SECTION N1100.A.5.2. PROVIDE AN ENERGY |
| CODE COMPLIANCE FORM AND COOLING LOAD CLACULATIONS IN |
| ACCORDANCE WITH THESE SECTIONS TO DEMONSTRATE |
| COMPLIANCE. |
| |
| 4. THE PROPOSED NEW AIR HANDLER APPEARS TO BE IN THE |
| ATTIC OF THE NEW GARAGE. THERE IS NO ACCESS FOR THIS |
| UNIT SHOWN ON PLANS. ACCESS SHALL BE PROVIDED WITH AN |
| OPENING AND UNOBSTRUCTED PASSAGEWAY LARGE ENOUGH TO |
| ALLOW REMOVAL OF THE APPLIANCE. THE PASSAGEWAY SHALL |
| NOT BE LESS THAN 30 INCHES HIGH AND 22 INCHES WIDE AND |
| NOT MORE THAN 6 FEET (1829 MM) IN LENGTH FROM THE ATTIC |
| ACCESS OPENING TO THE APPLIANCE'S SERVICE PANEL IN |
| ACCORDANCE WITH FBC-R SECTION M1305.1.3. A LUMINAIRE |
| CONTROLLED BY A SWITCH LOCATED AT THE REQUIRED |
| PASSAGEWAY OPENING AND A RECEPTACLE OUTLET SHALL BE |
| INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN |
| ACCORDANCE WITH FBC-R SECTION M1305.1.3.1. |
| |