Plan Review Notes
Plan Review Notes For Permit 09030254
Permit Number 09030254
Review Stop E
Sequence Number 1
Notes
Date Text
2009-03-27 12:25:09 
  
 APPLICATION #09030225 ELECTRICAL PLAN REVIEW
 310 CORDOVA ROAD 3/27/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 NOTE- ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN
 IS NEW OR EXISTING. IF NEW INCLUDE AN AIC RATING, AND
 LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER
 ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE
 WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} THERE DISCONNECTS ON THE RISER DIAGRAM LABELED 1ST
 AND 2ND FLOOR APARTMENTS, BUT NO PANEL SHOWN ON THE 2ND
 FLOOR PLAN, SHEET E2. LOCATE SAME OR INDICATE IF
 REMOVED. 215.5
  
 3} PROVIDE A LOAD CALCULATION AND PANEL SCHEDULES FOR
 THE ENTIRE SERVICE, INCLUDING THE APARTMENTS. 215.5,
 408.4.
  
 4} THE PANEL LOCATION IN THE APARTMENT ON SHEET E1 IS
 EITHER IN VIOLATION OF 240.24(E) BATHROOMS OR 110.26 IF
 FACING STUDIO 1.
  
 5} THE MAIN HOUSE PANEL LOCATED BEHIND THE STACK
 WASHER/DRYER IS IN VIOLATION OF 110.26 AND 240.24(D) IF
 THIS IS TO BE STORAGE ROOM.
  
 6} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN, ALL
 UNITS.
  
 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR EXAMPLES
 OF DEFICIENCIES.
  
 8} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 9} LABEL ALL ROOMS FOR CLARITY, RECORD RETENTION AND SO
 OUTLET REQUIREMENTS OF 210.52 CAN BE REVIEWED.
  
 10} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3).
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO
 REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  