| APPLICATION #09030225 ELECTRICAL PLAN REVIEW |
| 310 CORDOVA ROAD 3/27/09 |
| WEST PALM BEACH, FL. |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| NOTE- ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| OTHERWISE NOTED. |
| |
| 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN |
| IS NEW OR EXISTING. IF NEW INCLUDE AN AIC RATING, AND |
| LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER |
| ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE |
| WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| |
| 2} THERE DISCONNECTS ON THE RISER DIAGRAM LABELED 1ST |
| AND 2ND FLOOR APARTMENTS, BUT NO PANEL SHOWN ON THE 2ND |
| FLOOR PLAN, SHEET E2. LOCATE SAME OR INDICATE IF |
| REMOVED. 215.5 |
| |
| 3} PROVIDE A LOAD CALCULATION AND PANEL SCHEDULES FOR |
| THE ENTIRE SERVICE, INCLUDING THE APARTMENTS. 215.5, |
| 408.4. |
| |
| 4} THE PANEL LOCATION IN THE APARTMENT ON SHEET E1 IS |
| EITHER IN VIOLATION OF 240.24(E) BATHROOMS OR 110.26 IF |
| FACING STUDIO 1. |
| |
| 5} THE MAIN HOUSE PANEL LOCATED BEHIND THE STACK |
| WASHER/DRYER IS IN VIOLATION OF 110.26 AND 240.24(D) IF |
| THIS IS TO BE STORAGE ROOM. |
| |
| 6} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE |
| INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN, ALL |
| UNITS. |
| |
| 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR EXAMPLES |
| OF DEFICIENCIES. |
| |
| 8} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| DESIGNED. |
| |
| 9} LABEL ALL ROOMS FOR CLARITY, RECORD RETENTION AND SO |
| OUTLET REQUIREMENTS OF 210.52 CAN BE REVIEWED. |
| |
| 10} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3). |
| |
| PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO |
| REVIEW COMMENTS IN WRITING. |
| |