2009-04-22 16:03:27 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE. |
| |
| 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING |
| BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| DUE. |
| |
| 2- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| ***NOTE: THIS MAY BE RECORDED LATER AT TIME OF PERMIT |
| PICK UP. |
| |
| 3- OWES $4.84 FOR RADON FEES. CHAPTER 10D-91, FLORIDA |
| ADMINISTRATIVE CODE. |
| |
| 4- CURRENT CODE IN EFFECT IS THE 2007 FLORIDA |
| RESIDENTIAL CODE, NOT THE 2004. NEED TO REVISE DESIGN |
| CRITERIA AND EVERY RELEVANT NOTE ON SHEET S3 TO THE |
| 2007 CODES. |
| ***NOTE: SEE SEC. R301.1 OF 2007 FLORIDA RESIDENTIAL |
| CODE AND SEC. 1609.1.1 FBC 2007 TO DETERMINE WHICH |
| DESIGN CRITERIA IS GOING TO BE USED. |
| |
| 5- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) NEW SKYLIGHT AS SHOWN ON PLANS. NONE PROVIDED AT |
| THIS TIME. |
| |
| B) GARAGE DOORS. FLORIDA PRODUCT APPROVAL FL6218-R8 |
| SUBMITTED IS FOR CODE VERSION 2004. NEED TO PROVIDE |
| CURRENT 2007 CODE VERSION. |
| |
| C) FLAT ROOF. (1) FLORIDA PRODUCT APPROVAL FL735-R2 |
| SUBMITTED IS FOR 2004 CODE VERSION. NEED CURRENT 2007 |
| CODE VERSION. (2) NOA-06-0601.05 SUBMITTED IS FOR |
| CEMENTIOUS WOOD FIBER DECKS. PLANS SUBMITTED SPECIFY |
| PLYWOOD ROOF SHEATHING. NEED TO PROVIDE PRODUCT |
| APPROVAL FOR PROPER ROOF SHEATHING TYPE. (3) CLEARLY |
| IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE USED. |
| (4) IF APPROVED ASSEMBLY IS LIMITED BY GENERAL |
| LIMITATION #7, THEN NEED TO PROVIDE SIGNED AND SEALED |
| CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER |
| AREAS. SEE GENERAL LIMITATION #7 ON LAST PAGE OF NOA |
| SUBMITTED. (***NOTE: IF SELECTED ASSEMBLY IS LIMITED BY |
| GENERAL LIMITATION #9, THEN IT CAN'T BE USED BECAUSE |
| THIS LIMITATION DOESN'T ALLOW NAIL ENHANCING. SEE |
| GENERAL LIMITATION #9). (5) PROVIDE CURRENT PRODUCT |
| APPROVAL FOR INSULATION. FLORIDA PRODUCT APPROVAL |
| FL4205-R2 SUBMITTED IS FOR 2004 CODE VERSION. NEED TO |
| PROVIDE CURRENT 2007 CODE VERSION. |
| |
| D) INSWING DOOR AS SHOWN ON PLANS. PRODUCT APPROVAL |
| SUBMITTED IS FOR OUTSWING DOORS ONLY. |
| |
| 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ALL NEW OR RE-SUBMITTED PRODUCT APPROVALS AS REQUIRED |
| BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| |
| 7- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| 13-101.2.2 FBC 2007. |
| NOTE: PLEASE MAKE SURE ALL INFORMATION IS COMPLETE AND |
| SIGNED AND DATED BY THE PREPARER AND BY OWNER/AGENT. |
| |
| 8- REVISE DETAIL C/A6. WINDOW BUCK NEED TO PROVIDE FULL |
| SUPPORT TO THE WINDOW/DOOR FRAME AS REQUIRED BY SEC. |
| R613.6.1.1 OF 2007 FLORIDA RESIDENTIAL CODE. BEVELED |
| BUCKS DON'T PROVIDE FULL SUPPORT. REVISE AS REQUIRED. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |