Plan Review Notes For Permit 09030231 |
Permit Number |
09030231 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-03-13 10:49:25 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. PLEASE CLARIFY WHICH FASTENER IS PROPOSED, TOP AND | | BOTTOM. | | | | OPENING 1 STAETS "LAG 14S". OPENING 8 STATES "LAG ELCO | | 14'S". THE GENERAL INFORMATION ON THE INSTALLATION | | SCHEDULE STATES THAT WOOD LAGS, ELCO UTRAACONS, AND #14 | | SMS TEX SCREWS ARE PROPOSED. FOR OPENING 1, IS IT LAG | | ON THE THE TOP, #14 ON THE BOTTOM? IF THIS IS THE CASE, | | WHAT FASTENERS ARE PROPOSED FOR OPENING 8? OPENING 9 | | STATES "LAG 14" BUT SUBSTRATE IS WOOD/BLOCK. SMS 14 | | CANNOT BE USED IN BLOCK. | | | | 2. PLEASE NOTE THAT THE INFORMATION HIGHLIGHTED ON THE | | PRODUCT APPROVAL DOES NOT NECESSARILY CORROLATE WITH | | THIS JOB. FOR INSTANCE, C5 HIGHLIGHTED BUT NOT | | SPECIFIED ON THE INSTALLATION SCHEDULE. IT APPEARS THAT | | SMS #14 ARE PROPOSED, BUT NOT HIGHLIGHTED. HIGHLIGHTING | | IS OPTIONAL, ASSISTS WITH INSPECTIONS, BUT IF DONE | | SHOULD CORRELATE WITH THIS PARTICULAR JOB. | | | | 3. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, | | FAC9B72. PLEASE PRINT THE APPROVAL COVER SHEET FROM THE | | WEBSITE, TWO SETS. WWW.FLORIDABUILDING.ORG | | |
|