Plan Review Notes
Plan Review Notes For Permit 09030231
Permit Number 09030231
Review Stop B
Sequence Number 1
Notes
Date Text
2009-03-13 10:49:25****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE CLARIFY WHICH FASTENER IS PROPOSED, TOP AND
 BOTTOM.
  
 OPENING 1 STAETS "LAG 14S". OPENING 8 STATES "LAG ELCO
 14'S". THE GENERAL INFORMATION ON THE INSTALLATION
 SCHEDULE STATES THAT WOOD LAGS, ELCO UTRAACONS, AND #14
 SMS TEX SCREWS ARE PROPOSED. FOR OPENING 1, IS IT LAG
 ON THE THE TOP, #14 ON THE BOTTOM? IF THIS IS THE CASE,
 WHAT FASTENERS ARE PROPOSED FOR OPENING 8? OPENING 9
 STATES "LAG 14" BUT SUBSTRATE IS WOOD/BLOCK. SMS 14
 CANNOT BE USED IN BLOCK.
  
 2. PLEASE NOTE THAT THE INFORMATION HIGHLIGHTED ON THE
 PRODUCT APPROVAL DOES NOT NECESSARILY CORROLATE WITH
 THIS JOB. FOR INSTANCE, C5 HIGHLIGHTED BUT NOT
 SPECIFIED ON THE INSTALLATION SCHEDULE. IT APPEARS THAT
 SMS #14 ARE PROPOSED, BUT NOT HIGHLIGHTED. HIGHLIGHTING
 IS OPTIONAL, ASSISTS WITH INSPECTIONS, BUT IF DONE
 SHOULD CORRELATE WITH THIS PARTICULAR JOB.
  
 3. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72. PLEASE PRINT THE APPROVAL COVER SHEET FROM THE
 WEBSITE, TWO SETS. WWW.FLORIDABUILDING.ORG
  