Plan Review Notes For Permit 09030230 |
Permit Number |
09030230 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-04-08 22:23:37 | *****DENIED***** | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | EDITION. ADD TO CODE REFERENCES | | | | 2. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE | | (BASED ON NFPA 101 - LIFE SAFETY CODE - 2006 EDITION | | AND NFPA 1 - UNIFORM FIRE CODE - 2006 EDITION) SHALL BE | | REFERENCED. AMEND CODE REFERENCES TO REFLECT CURRENT | | EDITIONS | | | | 3. PLEASE INDICATE THE OCCUPANCY TYPE ( BUSINESS, | | MERCANTILE, ASSEMBLY, ETC.) AND OCCUPANT LOAD FOR THE | | EXISTING BUILDING AS WELL AS THE EXPANSION PROJECT | | SCOPE OF WORK. | | | | 4. WHAT WAS/IS THE OCCUPANCY TYPE FOR THE ADJOINING | | SUITE (#114)? | | | | 5. THE ACTUAL PROJECT SITE ADDRESS, INCLUDING THE SUITE | | NUMBER, SHALL BE INCLUDED IN THE TITLE BLOCK OF EACH | | SUBMITTED PLAN SHEET. PLEASE BE ADVISED THAT THE PARCEL | | CONTROL NUMBER (PCN) LISTED ON THE APPLICATION | | REGISTERS AS 215 SOUTH OLIVE AVENUE INSTEAD OF THE | | ACTUAL ADDRESS OF 215 NORTH OLIVE AVENUE AS LISTED ON | | THE PERMIT APPLICATION AND THE SUBMITTED PLANS. PLEASE | | CORRECT. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE ARESPONSE | | LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|