2009-04-08 22:23:37*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION. ADD TO CODE REFERENCES
  
 2. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE
 (BASED ON NFPA 101 - LIFE SAFETY CODE - 2006 EDITION
 AND NFPA 1 - UNIFORM FIRE CODE - 2006 EDITION) SHALL BE
 REFERENCED. AMEND CODE REFERENCES TO REFLECT CURRENT
 EDITIONS
  
 3. PLEASE INDICATE THE OCCUPANCY TYPE ( BUSINESS,
 MERCANTILE, ASSEMBLY, ETC.) AND OCCUPANT LOAD FOR THE
 EXISTING BUILDING AS WELL AS THE EXPANSION PROJECT
 SCOPE OF WORK.
  
 4. WHAT WAS/IS THE OCCUPANCY TYPE FOR THE ADJOINING
 SUITE (#114)?
  
 5. THE ACTUAL PROJECT SITE ADDRESS, INCLUDING THE SUITE
 NUMBER, SHALL BE INCLUDED IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET. PLEASE BE ADVISED THAT THE PARCEL
 CONTROL NUMBER (PCN) LISTED ON THE APPLICATION
 REGISTERS AS 215 SOUTH OLIVE AVENUE INSTEAD OF THE
 ACTUAL ADDRESS OF 215 NORTH OLIVE AVENUE AS LISTED ON
 THE PERMIT APPLICATION AND THE SUBMITTED PLANS. PLEASE
 CORRECT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE ARESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  