Plan Review Notes
Plan Review Notes For Permit 09030230
Permit Number 09030230
Review Stop B
Sequence Number 1
Notes
Date Text
2009-03-27 14:30:44 
 BUILDING PLAN REVIEW
 PERMIT: 09030230
 ADD: 215 N. OLIVE AVE.
 CONT: NEWBOLD CONSTRUCTION INC.
 TEL: (561)842-0033
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3/27/09
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH THE 2009 SUPPLEMENTS.
  
 3) 2007 FBC (EXISTING) 401.4 A DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF
 THIS CODE. THIS INFORMATION SHALL BE INDICATED ON THE
 PLANS. THE LEVEL OF ALTERATION SHOWN ON THE PLANS DOES
 NOT MATCH THE DRAWINGS. ALTERATION LEVEL 2 INCLUDE THE
 RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION
 OF ANY WINDOW OR DOOR, THE RECONFIGURATION OR EXTENSION
 OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT 2007 FBC (EXISTING) 404.1.
  
 4) THE DINNING AREAS FAIL TO INDICATE THE LOCATION OF
 THE ACCESSIBLE SEATING AND ACCESS AISLE WIDTH IN BOTH
 AREAS PER SECTION 11-5 FBC. THE NEW SALAD BAR SEEMS TO
 BE A SELF-SERVICE AREA; THEREFORE, IT SHALL BE
 INSTALLED PER SECTION 11-5.6 AND FIGURE 54. SHOW
 COMPLIANCE.
  
 5) SEATING SPACES FOR PEOPLE IN WHEELCHAIR SHALL COMPLY
 WITH SECTION 11-4.32.2, 11-4.32.3, 11-4.32.4 AND FIGURE
 45 AND 46: THE CLEAR FLOOR SPACE SHALL COMPLY WITH
 11-4.2.4.
  
 6) THE DRAWINGS NEED TO SHOW THE USE AND OCCUPANCY OF
 THE SPACE PER CHAPTER 3, THE OCCUPANT LOAD PER TABLE
 1004.1.1 AND THE TYPE OF CONSTRUCTION PER CHAPTER 6 AND
 TABLE 601. WHEN CALCULATING THE OCCUPANT LOAD, SEE
 1004.7 FOR FIXED SEATING. IF THERE IS A FIRE SPRINKLER
 SYSTEM IN THE BUILDING, IT SHALL BE STATED ON THE
 PLANS.
  
 7) WITH THE ADDITIONAL SQUARE FOOTAGE ADDED TO THE
 SPACE SHOW THE MEANS OF EGRESS ON THE LIFE SAFETY
 SHEET. THE EXIT ACCESS DOORS SHALL COMPLY WITH FBC
 SECTION 1015 IN REFERENCE TO THE LOCATION OF THE DOORS.
  
 8) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES VALUATION OF BUILDINGS
 SHALL BE THE TOTAL COST INCLUDING INTERIOR FINISHES
 ELECTRIC ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS
 OVERHEAD AND PROFIT EXCLUDING LAND. OUR VALUATION
 REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND MEANS COST
 ANALYSIS 108.3
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (805) 6676
 [email protected]
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved