Plan Review Notes
Plan Review Notes For Permit 09030209
Permit Number 09030209
Review Stop B
Sequence Number 1
Notes
Date Text
2009-03-11 14:40:25RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2008
 REVISIONS.
  
 1- AS OF MARCH 1ST, 2009 THE NEW CODE IN EFFECT IS THE
 2007 FLORIDA RESIDENTIAL CODE. PRODUCT APPROVAL FL6417
 SUBMITTED IS FOR 2004 CODE VERSION. NEED TO PROVIDE
 PRODUCT APPROVAL FOR 2007 CODE VERSION.
  
 2- REVISE INSTALLATION SCHEDULE SUBMITTED:
 A) ACCORDING TO PROPERTY APPRAISAL WEBSITE THIS HOUSE
 IS A CONCRETE BLOCK STRUCTURE, NOT WOOD FRAME. REVISE
 SUBSTRATE ON COLUMN #11 AS REQUIRED.
  
 B) REVISE EDGE DISTANCE ON COLUMN #8. COORDINATE WITH
 ITEM 2A ABOVE.
 **NOTE: COORDINATE SHUTTER SPAN ON COLUMN #6 AS
 REQUIRED TO GET MINIMUM EDGE DISTANCE REQUIRED. ALSO,
 TAKE INTO CONSIDERATION THAT EDGE DISTANCE EXCLUDES
 STUCCO THICKNESS.
  
 C) REVISE ANCHOR SPACING AS REQUIRED TO COORDINATE WITH
 ITEMS #2 A AND B ABOVE.
 ***NOTE: USE THE HOLLOW CONCRETE BLOCK TABLE FOR
 CONCRETE BLOCK AND STUCCO CONSTRUCTION NOT THE CONCRETE
 TABLE.
  
 D) REVISE INFORMATION ON TOP OF INSTALLATION SCHEDULE
 SUBMITTED. SEE COMMENTS. REVISE TYPE OF CONSTRUCTION OR
 ATTACHMENT SURFACE. THIS HOUSE IS MASONRY, NOT WOOD
 FRAME. ALSO, WRITE CORRECT PRODUCT APPROVAL NUMBER.
 INFORMATION SUBMITTED IS FOR THE CONTRACTOR LICENSE
 NUMBER. SEE COMMENTS ON INSTALLATION SCHEDULE.
  
 E) PROVIDE 2 COPIES OF INSTALLATION SCHEDULE. ONLY ONE
 SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  
  
  