2009-03-11 14:40:25 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2008 |
| REVISIONS. |
| |
| 1- AS OF MARCH 1ST, 2009 THE NEW CODE IN EFFECT IS THE |
| 2007 FLORIDA RESIDENTIAL CODE. PRODUCT APPROVAL FL6417 |
| SUBMITTED IS FOR 2004 CODE VERSION. NEED TO PROVIDE |
| PRODUCT APPROVAL FOR 2007 CODE VERSION. |
| |
| 2- REVISE INSTALLATION SCHEDULE SUBMITTED: |
| A) ACCORDING TO PROPERTY APPRAISAL WEBSITE THIS HOUSE |
| IS A CONCRETE BLOCK STRUCTURE, NOT WOOD FRAME. REVISE |
| SUBSTRATE ON COLUMN #11 AS REQUIRED. |
| |
| B) REVISE EDGE DISTANCE ON COLUMN #8. COORDINATE WITH |
| ITEM 2A ABOVE. |
| **NOTE: COORDINATE SHUTTER SPAN ON COLUMN #6 AS |
| REQUIRED TO GET MINIMUM EDGE DISTANCE REQUIRED. ALSO, |
| TAKE INTO CONSIDERATION THAT EDGE DISTANCE EXCLUDES |
| STUCCO THICKNESS. |
| |
| C) REVISE ANCHOR SPACING AS REQUIRED TO COORDINATE WITH |
| ITEMS #2 A AND B ABOVE. |
| ***NOTE: USE THE HOLLOW CONCRETE BLOCK TABLE FOR |
| CONCRETE BLOCK AND STUCCO CONSTRUCTION NOT THE CONCRETE |
| TABLE. |
| |
| D) REVISE INFORMATION ON TOP OF INSTALLATION SCHEDULE |
| SUBMITTED. SEE COMMENTS. REVISE TYPE OF CONSTRUCTION OR |
| ATTACHMENT SURFACE. THIS HOUSE IS MASONRY, NOT WOOD |
| FRAME. ALSO, WRITE CORRECT PRODUCT APPROVAL NUMBER. |
| INFORMATION SUBMITTED IS FOR THE CONTRACTOR LICENSE |
| NUMBER. SEE COMMENTS ON INSTALLATION SCHEDULE. |
| |
| E) PROVIDE 2 COPIES OF INSTALLATION SCHEDULE. ONLY ONE |
| SUBMITTED. |
| |