Plan Review Notes For Permit 09030188 |
Permit Number |
09030188 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-03-11 10:17:22 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. | | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE. | | | | 1- REVISE INSTALLATION SCHEDULE SUBMITTED: | | A) EDGE DISTANCE SPECIFIED ON COLUMN EIGHT IS 2". | | ACCORDING TO ANCHOR SCHEDULE FOR CONCRETE BLOCK ON | | SHEET 11 OF 11 THERE IS NOT 2" EDGE DISTANCE FOR 1/4" X | | 3-1/4" ITW TAPCON. SHEET 11 OF 11 SHOWS EITHER 1" OR | | 2-1/2" EDGE DISTANCE. REVISE AS REQUIRED. | | ***NOTE: REVISE SHUTTER SPAN ON COLUMN SIX AS REQUIRED | | TO OBTAIN THE SPECIFIED EDGE DISTANCE. ALSO, KEEP IN | | CONSIDERATION THAT THE EDGE DISTANCE EXCLUDES THE | | STUCCO THICKNESS. | | | | B) REVISE ANCHOR SPACING AS REQUIRED TO MATCH | | INFORMATION SHOWN ON SHEET 11 OF 11 OF ACCORDION | | SHUTTERS. | | | | C) PROVIDE LEGIBLE COPY OF SHEET 11 OF 11 OF ACCORDION | | SHUTTERS. ONE SUBMITTED IS VERY BLURRY. | | | | 2- CLARIFY HOW IS OPENING #4 COMPLYING WITH THE EGRESS | | REQUIREMENTS OF SEC. R310.4 OF 2007 FLORIDA RESIDENTIAL | | CODE IF ACCORDION SHUTTERS ARE INSTALLED ON IT. | | ***NOTE: KEEP IN CONSIDERATION DOOR SWING DIRECTION. | | SHOW SWING ON KEY PLAN PROVIDED. | | | | 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | FLORIDA STATUTE. | | | | 4- PROVIDE 2 COPIES OF INSTALLATION SCHEDULE. ONLY ONE | | COPY SUBMITTED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|