Plan Review Notes For Permit 09030188
Permit Number 09030188
Review Stop B
Sequence Number 1
Notes
Date Text
2009-03-11 10:17:22RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE.
  
 1- REVISE INSTALLATION SCHEDULE SUBMITTED:
 A) EDGE DISTANCE SPECIFIED ON COLUMN EIGHT IS 2".
 ACCORDING TO ANCHOR SCHEDULE FOR CONCRETE BLOCK ON
 SHEET 11 OF 11 THERE IS NOT 2" EDGE DISTANCE FOR 1/4" X
 3-1/4" ITW TAPCON. SHEET 11 OF 11 SHOWS EITHER 1" OR
 2-1/2" EDGE DISTANCE. REVISE AS REQUIRED.
 ***NOTE: REVISE SHUTTER SPAN ON COLUMN SIX AS REQUIRED
 TO OBTAIN THE SPECIFIED EDGE DISTANCE. ALSO, KEEP IN
 CONSIDERATION THAT THE EDGE DISTANCE EXCLUDES THE
 STUCCO THICKNESS.
  
 B) REVISE ANCHOR SPACING AS REQUIRED TO MATCH
 INFORMATION SHOWN ON SHEET 11 OF 11 OF ACCORDION
 SHUTTERS.
  
 C) PROVIDE LEGIBLE COPY OF SHEET 11 OF 11 OF ACCORDION
 SHUTTERS. ONE SUBMITTED IS VERY BLURRY.
  
 2- CLARIFY HOW IS OPENING #4 COMPLYING WITH THE EGRESS
 REQUIREMENTS OF SEC. R310.4 OF 2007 FLORIDA RESIDENTIAL
 CODE IF ACCORDION SHUTTERS ARE INSTALLED ON IT.
 ***NOTE: KEEP IN CONSIDERATION DOOR SWING DIRECTION.
 SHOW SWING ON KEY PLAN PROVIDED.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 4- PROVIDE 2 COPIES OF INSTALLATION SCHEDULE. ONLY ONE
 COPY SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER