Plan Review Notes For Permit 09030171 |
Permit Number |
09030171 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-03-12 15:21:48 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. IT APPEARS THAT THIS JOB IS EXPOSURE C, FBC | | R301.2.1.4, FBC 1609. PLEASE CONFIRM THAT ANCHOR | | SPACING SPECIFIED COMPLIES WITH EXPOSURE C PRESSURES. | | ALTHOUGH INSTALLATION SCHEDULE STATES THAT DESIGN | | CRITERIA IS -47.2, THE ROW FOR -57 IS USED FOR -47.2 | | PRESSURE SO IT IS LIKELY THAT PROPOSED ANCHOR SPACING | | IS COMPLIANT. TO AVOID CONFUSION, PLEASE REVISE | | INSTALLATION SCHEDULE. (NOTE PLANS WOULD NOT HAVE | | FAILED FOR THIS COMMENT ALONE - THIS IS ALSO ADVISORY | | TO CONFIRM EXPOSURE CLASSIFICATION FOR FUTURE PERMIT | | APPLICATIONS.) | | | | 2. OPENINGS 1 THROUGH 7, ANCHOR SPACING INFORMATION NOT | | PROVIDED (LEFT BLANK). PLEASE PROVIDE THE REQUIRED | | INFORMATION. | | | | |
|