Date |
Text |
2009-05-08 14:36:20 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| COMMENTS FROM FIRST REVIEW NOT ADDRESSED: |
| |
| 1. (PREVIOUSLY #6, FIRST REVIEW) THE APPLICATION DOES |
| NOT GIVE CLEAR DESCRIPTOIN OF THE INTENDED WORK OF THE |
| AREA. BOTH THE APPLICATION AND THE DRAWINGS SHALL |
| CLEARLY SHOW IN DETAIL THE LOCATION AND AREA OF THE |
| PROPOSED CHANGES. PROVIDE A WALL LEGEND CLEARLY |
| INDICATING THE NEW WALLS AND EXISTING WALL WITH |
| DESCRIPTION OF ALL MATERIALS. THE DRAWINGS SHALL ALSO |
| STATE THE USE OF EACH ROOM OF THE SPACE. |
| |
| 2ND REVIEW, NO WALL LEGEND PROVIDED. SOME WALLS ARE |
| SHOWN IN GREY, SOME IN BLACK, AND SOME ARE DOUBLE |
| BLACKLINE. WHICH ARE NEW, EXISTING? SCOPE IS NOT CLEAR; |
| PLEASE PROVIDE WALL LEGEND. |
| |
| 2. THE NEW CLOSET DOOR (DOOR 2) INTERFERES WITH THE |
| DOOR SWING OF THE BATHROOM DOOR FBC1005, AND THE |
| PROPOSED NEW (CLOSET) WALL OBSTRUCTS THE REQUIRED |
| MANEUVERING CLEARANCE, PULL SIDE, FBC11 FIGURE 25. IT |
| APPEARS THAT REVERSING THE BATHROOM DOOR MAY RESOLVE |
| THE ISSUE, BUT ANY CODE COMPLIANT OPTION IS ACCEPTABLE. |
| |
| 3. THE RAMP HANDRAILS LACK THE REQUIRED EXTENSION, |
| FBC11-4.8.5(2). |
| |
| 4. FBC11-4.28.2, VISUAL ALARM REQUIRED IN BATHROOM. |
| (NEW COMMENT, CAN BE PROVISO/REDLINE.) |
| |
| 5. PLEASE NOTE THAT IT IS POSSIBLE THAT THIS REVIEW CAN |
| BE PASSED WITH PROVISO/REDLINE (REVISION REQUIRED), |
| PLEASE CONTACT ME IF THIS APPLICATION PASSES ALL OTHER |
| TRADES. |
| |
| 6. PLEASE PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. |
| FBC*106. |