Plan Review Notes
Plan Review Notes For Permit 09030109
Permit Number 09030109
Review Stop B
Sequence Number 2
Notes
Date Text
2009-05-08 14:36:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM FIRST REVIEW NOT ADDRESSED:
  
 1. (PREVIOUSLY #6, FIRST REVIEW) THE APPLICATION DOES
 NOT GIVE CLEAR DESCRIPTOIN OF THE INTENDED WORK OF THE
 AREA. BOTH THE APPLICATION AND THE DRAWINGS SHALL
 CLEARLY SHOW IN DETAIL THE LOCATION AND AREA OF THE
 PROPOSED CHANGES. PROVIDE A WALL LEGEND CLEARLY
 INDICATING THE NEW WALLS AND EXISTING WALL WITH
 DESCRIPTION OF ALL MATERIALS. THE DRAWINGS SHALL ALSO
 STATE THE USE OF EACH ROOM OF THE SPACE.
  
 2ND REVIEW, NO WALL LEGEND PROVIDED. SOME WALLS ARE
 SHOWN IN GREY, SOME IN BLACK, AND SOME ARE DOUBLE
 BLACKLINE. WHICH ARE NEW, EXISTING? SCOPE IS NOT CLEAR;
 PLEASE PROVIDE WALL LEGEND.
  
 2. THE NEW CLOSET DOOR (DOOR 2) INTERFERES WITH THE
 DOOR SWING OF THE BATHROOM DOOR FBC1005, AND THE
 PROPOSED NEW (CLOSET) WALL OBSTRUCTS THE REQUIRED
 MANEUVERING CLEARANCE, PULL SIDE, FBC11 FIGURE 25. IT
 APPEARS THAT REVERSING THE BATHROOM DOOR MAY RESOLVE
 THE ISSUE, BUT ANY CODE COMPLIANT OPTION IS ACCEPTABLE.
  
 3. THE RAMP HANDRAILS LACK THE REQUIRED EXTENSION,
 FBC11-4.8.5(2).
  
 4. FBC11-4.28.2, VISUAL ALARM REQUIRED IN BATHROOM.
 (NEW COMMENT, CAN BE PROVISO/REDLINE.)
  
 5. PLEASE NOTE THAT IT IS POSSIBLE THAT THIS REVIEW CAN
 BE PASSED WITH PROVISO/REDLINE (REVISION REQUIRED),
 PLEASE CONTACT ME IF THIS APPLICATION PASSES ALL OTHER
 TRADES.
  
 6. PLEASE PROVIDE A COPY OF THE CONTRACT FOR THIS JOB.
 FBC*106.