2009-03-13 16:27:07 | BUILDING PLAN REVIEW |
| PERMIT: 09030109 |
| ADD: 1804 N. DIXIE HWY UNIT C |
| CONT: HOLEMAN HOMES INC. |
| TEL: (561)743-0687 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2007 FBC |
| BUILDING WITH THE 2009 SUPPLEMENTS. THE DESIGN UNDER |
| WHICH THE PROJECT IS BASE SHALL BE STATED ON THE PLANS. |
| |
| 4) 2007 FBC (EXISTING) 401.4 A DESIGN PROFESSIONAL OR |
| AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF |
| THIS CODE. THIS INFORMATION SHALL BE INDICATED ON THE |
| PLANS. |
| |
| 5) THE PLANS SHALL INDICATE THE TYPE OF CONSTRUCTION |
| PER CHAPTER 6 AND TABLE 503, THE USE AND OCCUPANCY PER |
| CHAPTER 3. THIS INFORMATION IS REQUIRED SO THAT ANY |
| ADDITIONAL CONSTRUCTION IN ACCORDANCE WITH THE ORIGINAL |
| BUILDING TYPE. |
| |
| 6) THE APPLICATION DOES NOT GIVE CLEAR DESCRIPTION OF |
| THE INTENDED WORK OF THE AREA. BOTH THE APPLICATION AND |
| THE DRAWINGS SHALL CLEARLY SHOW IN DETAIL THE LOCATION |
| AND AREA OF THE PROPOSED CHANGES. PROVIDE A WALL LEGEND |
| CLEARLY INDICATING THE NEW WALLS AND THE EXISTING WALL |
| WITH A DESCRIPTION OF ALL MATERIALS. THE DRAWINGS SHALL |
| ALSO STATE THE USE OF EACH ROOM OF THE SPACE. THE PLANS |
| SHOW A SECTION OF A MEZZANINE, PLEASE INDICATE CLEARLY |
| THE LOCATION OF THE MEZZANINE ON THE DRAWINGS. THE |
| DOCUMENTS SHALL CLEARLY SHOW THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED FBC 106.1.1 |
| |
| 7) SHEET 1.0A SHOWS A SECTION FOR A RAISED PLATFORM ON |
| 2 X 8 WITH ?? INCH PLYWOOD. THE PLATFORM SHALL BE |
| CONSTRUCTED IN ACCORDANCE WITH FBC 2007 410.3 AND |
| 410.4. INDICATE THE USE OF THE PLATFORM ON THE |
| DRAWINGS. SHOW THE ACCESSIBILITY ENTRANCE TO THE |
| PLATFORM FBC 11-4.1.2 VERTICAL ACCESSIBILITY, SHALL BE |
| PROVIDED TO ALL LEVELS ABOVE OR BELOW THE OCCUPIAABLE |
| GRADE LEVEL. SHOW COMPLIANCE. HANDRAILS MAY BE REQUIRED |
| WHEN ADDITIONAL INFORMATION SHOWN WITH THE HEIGHT AND |
| USE OF THE PLATFORM. |
| |
| 8) THERE ARE SOME SYMBOLS ON THE PLANS WITH NUMBERS |
| INSIDE, IF THESE SYMBOLS ARE MAKING REFERENCE TO |
| DETAILS PROVIDE THE DETAIL DRAWINGS. |
| |
| 9) PROVIDE THE CONNECTION DETAIL OF THE 2 X 8 TO THE |
| EXISTING FLOOR AND EXISTING WALLS WITH THE TYPES OF |
| CONNECTION STRAPS; AND THE NAIL PATTERN FOR THE |
| PLYWOOD. STATE THE TYPE OF WOOD TO BE USED AND THE TYPE |
| OF EXISTING FLOOR. THE UNIFORM DISTRIBUTED LIVE LOAD |
| SHALL BE GIVEN PER TABLE 1067.1, ALONG WITH THE LATERAL |
| SUPPORT PER 2308.8.5 AND THE GRADE/ SPECIES AND NUMBER |
| FOR THE TYPE OF WOOD USED FBC 2304.7.1. |
| |
| NOTE: ADDITIONAL NOTES MAY APPEAR ON SECOND REVIEW |
| DEPENDING ON THE RESPONSE TO THE ABOVE NOTES. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| PHONE (561)805-6726 |
| FAX (561) 805-6676 |
| [email protected] |
| |
| |
| |
| |