2009-04-06 11:10:03 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| PLEASE SEE COMMENT FROM REVIEW OF MASTER PERMIT; |
| 09010024, AND PREVIOUS ROOF PERMIT REVIEW : |
| |
| |
| 1. CONTRACTOR MUST SELECT AN APPROVED ASSEMBLY AND |
| SPECIFY ENHANCED FASTENING. |
| |
| A DIFFERENT NOA WAS SUBMITTED, ASSEMBLY SELECTED WHICH |
| MEETS A MAXIMUM DESIGN PRESSURE OF -52.5PSF. ENGINEER'S |
| REQUIREMENT FOR ZONES 2 AND 3 IS -79.2PSF. PLEASE |
| ADDRESS THE FOLLOWING: |
| |
| A. CLARIFY WHY ZONE 3 IS LOW; SEE FBC TABLE 1609.6.2.1 |
| (-89PSF REQUIRED FOR ZONE 3). CONTRACTOR MAY REMOVE THE |
| ENGINEERING AND USE FBC TABLE 1609.6.2.1 FOR DESIGN |
| PRESSURES FOR THE ROOF, OR ENGINEER CAN CLARIFY TO USE |
| -79PSF (PROVIDE CALCULATIONS). |
| |
| B. SPECIFY ENHANCED FASTENING FOR CORNER AND PERIMETER |
| ZONES. |
| |
| 2. A NEW NOA SUBMITTED; PLEASE HAVE THIS REVIEWED BY |
| DESIGNER OF RECORD FBC*106.3.3. |
| |
| 3. AS THIS IS A CHANGE TO THE MASTER PERMIT, THIS WILL |
| BE SUBMITTED AS A REVISION TO THE MASTER. INFORMATIONAL |
| ONLY. |
| |
| |
| |