2009-04-06 11:10:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 PLEASE SEE COMMENT FROM REVIEW OF MASTER PERMIT;
 09010024, AND PREVIOUS ROOF PERMIT REVIEW :
  
  
 1. CONTRACTOR MUST SELECT AN APPROVED ASSEMBLY AND
 SPECIFY ENHANCED FASTENING.
  
 A DIFFERENT NOA WAS SUBMITTED, ASSEMBLY SELECTED WHICH
 MEETS A MAXIMUM DESIGN PRESSURE OF -52.5PSF. ENGINEER'S
 REQUIREMENT FOR ZONES 2 AND 3 IS -79.2PSF. PLEASE
 ADDRESS THE FOLLOWING:
  
 A. CLARIFY WHY ZONE 3 IS LOW; SEE FBC TABLE 1609.6.2.1
 (-89PSF REQUIRED FOR ZONE 3). CONTRACTOR MAY REMOVE THE
 ENGINEERING AND USE FBC TABLE 1609.6.2.1 FOR DESIGN
 PRESSURES FOR THE ROOF, OR ENGINEER CAN CLARIFY TO USE
 -79PSF (PROVIDE CALCULATIONS).
  
 B. SPECIFY ENHANCED FASTENING FOR CORNER AND PERIMETER
 ZONES.
  
 2. A NEW NOA SUBMITTED; PLEASE HAVE THIS REVIEWED BY
 DESIGNER OF RECORD FBC*106.3.3.
  
 3. AS THIS IS A CHANGE TO THE MASTER PERMIT, THIS WILL
 BE SUBMITTED AS A REVISION TO THE MASTER. INFORMATIONAL
 ONLY.
  
  
  