2009-03-16 08:32:13 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| PLEASE SEE COMMENT FROM REVIEW OF MASTER PERMIT; |
| 09010024, AND PREVIOUS ROOF PERMIT REVIEW: |
| |
| |
| 5. CONTRACTOR MUST SELECT AN APPROVED ASSEMBLY AND |
| SPECIFY ENHANCED FASTENING. |
| |
| CONTRACTOR SUBMITTED NOA 060613.06 FOR THE FLAT DECK |
| WITH THE MASTER PERMIT AND HIGHLIGHTED THE ASSEMBLY ON |
| PAGE 12 (INSULATED DECK). THIS ASSEMBLY HAS A DESIGN |
| PRESSURE LIMITATION OF -60PSF. SEE GENERAL LIMITATION |
| #7 ON THE NOA, CALCULATIONS FOR ENHANCED FASTENING FOR |
| PERIMETER AND CORNER ZONES ARE TO BE CALCULATED BY AN |
| ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT. |
| |
| DELEGATED ENGINEERING (ENHANCED FASTENING CALCULATIONS) |
| ARE TO BE REVIEWED BY ENGINEER OF RECORD FAC61G15-31. |
| |
| 2ND ROOF PERMIT REVIEW, ENGINEERING SPECIFYING ROOF |
| PRESSURES WAS SUBMITTED AS WELL AS ROOF SHEATHING |
| NAILING PATTERN. THIS SHOULD HAVE BEEN INCLUDED ON THE |
| MASTER PERMIT; THIS DOES NOT ADDRESS THE COMMENT. |
| CALCULATIONS IN ACCORDANCE WITH RAS117 FOR THE |
| INSULATION BOARD IS REQUIRED. ZONES 2 AND 3 HAVE A |
| DESIGN PRESSURE OF -79.2, BUT THE ASSEMBLY SELETED HAS |
| A DESIGN PRESSURE LIMITATION OF -60PSF. ENHANCED |
| FASTENING IN ACCORDANCE WITH RAS117 REQUIRED FOR THIS |
| ASSEMBLY (-60PSF) TO MEET THE DESIGN PRESSURE (-79.2). |
| |
| SEE PAGE 20 OF THE NOA, ITEM 7: |
| |
| PERMIETER AND CORNER AREAS SHALL COMPLY WITH THE |
| ENHANCED UPLIFT PRESSURE REQUIREMENTS OF THESE AREAS. |
| FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| INSULATION AND BASE SHEET AS CALCULATED IN COMPLIANCE |
| WITH ROOFING APPLICATION STANDARD RAS 117. CALCULATIONS |
| PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, OR |
| REGISTERED ROOF CONSLUTANT. |
| |
| THE ENGINEERING SUBMITTED IS ENTITLED "ROOF AND WALL |
| NAILING SCHEDULE." THIS IS ROOF SHEATHING NAILING |
| SCHEDULE, NOT THE ROOF ASSEMBLY NAILING SCHEDULE. THIS |
| APPLIES TO THE PLYWOOD INSTALLATION, NOT THE ROOF |
| ASSEMBLY (TAMKO BUR ROOFING SYSTEM) INSTALLATION. |
| |
| |
| |