2009-03-05 16:19:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | PLEASE SEE COMMENT FROM REVIEW OF MASTER PERMIT; | | 09010024: | | | | | | 5. PRODUCT APPROVALS REQUIRED FOR THE FLAT ROOF, | | PITCHED ROOF FAC9B72. FOR THE FLAT DECK, CONTRACTOR | | MUST SELECT AN APPROVED ASSEMBLY AND SPECIFY ENHANCED | | FASTENING IF NECESSARY. THIS MAY BE DONE WITH THE ROOF | | PERMIT APPLICATION; THIS INFORMATION IS REQUIRED BEFORE | | A ROOF PERMIT CAN BE ISSUED. | | | | CONTRACTOR SUBMITTED NOA 060613.06 FOR THE FLAT DECK | | WITH THE MASTER PERMIT AND HIGHLIGHTED THE ASSEMBLY ON | | PAGE 12 (INSULATED DECK). THIS ASSEMBLY HAS A DESIGN | | PRESSURE LIMITATION OF -60PSF. SEE GENERAL LIMITATION | | #7 ON THE NOA, CALCULATIONS FOR ENHANCED FASTENING FOR | | PERIMETER AND CORNER ZONES ARE TO BE CALCULATED BY AN | | ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT. | | | | DELEGATED ENGINEERING (ENHANCED FASTENING CALCULATIONS) | | ARE TO BE REVIEWED BY ENGINEER OF RECORD FAC61G15-31. | | |
|