Plan Review Notes
Plan Review Notes For Permit 09030061
Permit Number 09030061
Review Stop B
Sequence Number 2
Notes
Date Text
2009-04-13 13:55:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE DOOR, FAC9B72.
  
 PLEASE NOTE THAT IF THIS COMMENT IS NOT ADDRESSED PRIOR
 TO PERMIT ISSUANCE, PERMIT WILL BE ISSUED WITH PROVISO.
  
 2. ADDRESSED.
  
 3. 1ST REVIEW - SHEATHING DOES NOT COMPLY WITH FBC R
 TABLE 803.1, PAGE 3.
  
 2ND REVIEW - PLEASE CLARIFY; SHEATHING SPECIFIED AS
 7/16" OSB, BUT FBC R TABLE 803.1 REQUIRES MINIMUM
 THICKNESS FOR 24" SPAN TO BE 5/8".
  
 4. 1ST REVIEW - ROOF NAIL SIZE DOES NOT COMPLY WITH FBC
 R 803.2.3.1, PAGE 3.
  
 2ND REVIEW - PLEASE CLARIFY; 6D NAILS SPECIFIED, BUT
 FBC R803.2.3.1 REQUIRES MINIMUM 8D.
  
 ****PLEASE CONTACT ME IF YOU DISAGREE WITH THESE
 COMMENTS; A RESPONSE LETTER WAS NOT SUBMITTED SO IT IS
 NOT CLEAR WHY ITEMS WERE NOT REVISED***
 ****OFFERED TO CONTRACTOR TO ISSUE PERMIT WITH PROVISO,
 WILL REDLINE/ENGINEER TO SUBMIT REVISED DRAWING WITH
 CHANGES***
  
 NEW COMMENTS:
  
 5. TRUSS ENGINEERING INCLUDES A COMPANY NAME.
 CERTIFICATE OF AUTHORIZATION REQUIRED TO PRACTICE
 ENGINEERING THROUGH A COMPANY, FS471.
  
 6. TRUSS ENGINEERING INDEX SHEET IS TO INCLUDE ALL
 INFORMATION REQUIRED BY FAC61G15-31.003. THIS CAN BE
 VIEWED AT WWW.FBPE.ORG, LAWS AND RULES.
  
 7. PLEASE ADVISE AS TO STANDARDS THAT WERE USED FOR
 THIS CALCULATION. THE SOFTWARE USED IS OUTDATED; THIS
 IS ACCEPTABLE (IF CODE COMPLIANT) BUT PLEASE NOTE THAT
 SOME TRUSS ENGINEERING SOFTWARE UTILIZED A STRESS
 INCREASE UNTIL APPROXIMATELY 2004.
  
 ****NOTE THAT ALL COMMENTS REGARDING TRUSS ENGINEERING
 CAN BE A PROVISO ITEM - TRUSS ENGINEERING TO BE
 SUBMITTED AS A REVISION PRIOR TO INSTALLATION****
  
 8. PLEASE SEE FS553.80(2)(B), A 4X PLAN REVIEW IS
 REQUIRED AFTER THIRD REVIEW.
  
  