2009-07-24 16:39:05** PROVISO **
  
 1) NOTE: THE LIGHTING LEVELS AT STAIR TREAD AREAS HAVE
 STILL NOT BEEN IDENTIFIED ON PLANS. THE FLAT AREAS HAVE
 BEEN SHOWN HOWEVER BASED ON THE CHANGES IN NFPA-101 THE
 LIFE SAFETY CODE ALL AREAS OF THE TREADS MUST MEET
 7.8.1.3 UNDER NORMAL CONDITIONS.
 THIS MAY BE PROVIDED ON A DETAIL FOR THE STAIRS ALONE.
 OTHER AREAS ARE OK>
  
 ** THE ABOVE MUST BE PROVIDED BEFORE INSPECTIONS. KEEP
 IN MIND ANY ADDITIONAL LIGHTING WHICH MAY BE REQUIRED
 TO BE ADDED IS AT THE RISK OF THE CONTRACTOR.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  