Plan Review Notes
Plan Review Notes For Permit 09030018
Permit Number 09030018
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-04-01 20:37:08*****DENIED*****
  
  
 1. AS OF 12/31/2008, THE 2007 EDITION OF FLORIDA FIRE
 PREVENTION CODE (WHICH IS BASED ON NFPA 101, LIFE
 SAFETY CODE - 2006 EDITION AND NFPA 1 - UNIFORM FIRE
 CODE - 2006 EDITION) SHALL BE REFERENCED.
  
 2. ON THE COVER PAGE, AMEND THE FOLLOWING: NOTE #1 TO
 READ THAT - STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS SHALL COMPLY WITH
 NFPA 241 - 2004 EDITION ; NOTE #2 - CORRECT SPELLING OF
 FREQUENTLY, NOT FRECUENTLY; #5 - UPDATE TO THE 2006
 EDITION OF NFPA 101; #6 - CORRECT SPELLING OF BELOW,
 NOT BELLOW.
  
 3. SHOW THE LOCATION OF THE PROPOSED MEZZANINE IN
 RELATION TO THE NEAREST EXIT DOOR.
  
 4. PROVIDE THE PRESCRIPTIVE STRENGTHS FOR THE HANDRAILS
 AND GUARDRAILS FOR THE MEZZANINE STAIRS.
  
 5. PLEASE BE ADVISED THAT ALL SUBMITTED PLAN SHEETS
 UNDER THIS PERMIT SHALL BE SEALED, STAMPED, AND SIGNED.
 THIS IS NOT OBSERVED ON FP-1 SHEET.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW