Plan Review Notes For Permit 09030018 |
Permit Number |
09030018 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-04-01 20:37:08 | *****DENIED***** | | | | | | 1. AS OF 12/31/2008, THE 2007 EDITION OF FLORIDA FIRE | | PREVENTION CODE (WHICH IS BASED ON NFPA 101, LIFE | | SAFETY CODE - 2006 EDITION AND NFPA 1 - UNIFORM FIRE | | CODE - 2006 EDITION) SHALL BE REFERENCED. | | | | 2. ON THE COVER PAGE, AMEND THE FOLLOWING: NOTE #1 TO | | READ THAT - STRUCTURES UNDERGOING CONSTRUCTION, | | ALTERATION, OR DEMOLITION OPERATIONS SHALL COMPLY WITH | | NFPA 241 - 2004 EDITION ; NOTE #2 - CORRECT SPELLING OF | | FREQUENTLY, NOT FRECUENTLY; #5 - UPDATE TO THE 2006 | | EDITION OF NFPA 101; #6 - CORRECT SPELLING OF BELOW, | | NOT BELLOW. | | | | 3. SHOW THE LOCATION OF THE PROPOSED MEZZANINE IN | | RELATION TO THE NEAREST EXIT DOOR. | | | | 4. PROVIDE THE PRESCRIPTIVE STRENGTHS FOR THE HANDRAILS | | AND GUARDRAILS FOR THE MEZZANINE STAIRS. | | | | 5. PLEASE BE ADVISED THAT ALL SUBMITTED PLAN SHEETS | | UNDER THIS PERMIT SHALL BE SEALED, STAMPED, AND SIGNED. | | THIS IS NOT OBSERVED ON FP-1 SHEET. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | |
|