Plan Review Notes
Plan Review Notes For Permit 09030014
Permit Number 09030014
Review Stop B
Sequence Number 1
Notes
Date Text
2009-03-02 17:03:21RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE.
  
 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. NEED TO UPDATE PERMIT VALUATION AS REQUIRED BY
 SEC. 108 OF 2004 FBC AND CITY OF WEST PALM BEACH
 ORDINANCE.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FL. ST.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR WINDOW MULLIONS IN LIVING ROOM AND
 BEDROOM #1.
  
 4- SPECIFY TYPE OF EXISTING WINDOWS TO BE REPLACED.
 SPECIALLY THE BEDROOM WINDOWS TO VERIFY COMPLIANCE WITH
 THE EGRESS REQUIREMENTS OF SEC. 501.3 OF 2007 FLORIDA
 EXISTING BUILDING CODE.
  
 5- PROVIDE 2 COPIES OF SINGLE HUNG WINDOWS NOA
 06-1121.14. ONLY ONE COPY SUBMITTED. OTHER COPY
 SUBMITTED NOA 05-0930.03 IS EXPIRED, THEREFORE IT CAN
 BE USED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712