Plan Review Notes For Permit 09020635 |
Permit Number |
09020635 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-07-24 19:49:28 | * DENIED REVISION ** | | | | 1) NOTE: FAMILY ROOM ON ORIGINAL PLANS AND REVISIONS | | INDICATING 2.1 INCLUDES THE DECRETIVE ALLOWANCES UNDER | | THE 2004 FBC. ONLY IF THIS PROJECT WAS UNDER THE 2007 | | FBC WOULD THE LIGHTING ALLOWANCE BE EXCEEDED. | | | | 2) NOTE: THE PREVIOUS PLANS INDICATED ROOM #241 AS | | FAMILY ROOM WITH OTHER ITEMS SUCH AS ADDITIONAL | | SWITCHES AND ADDITIONAL FIXTURES. THE ROOM 241 WAS | | REVISED FROM PLANS ON FILE HOWEVER NO REVISION HAS BEEN | | INDICATED AT THIS LOCATION. SWITCHES, FIXTURES ETC HAVE | | BEEN REMOVED. | | OTHER LOCATIONS WOULD BE HALLWAY 242 ALSO IN WHICH | | FIXTURES HAVE BEEN REMOVED HOWEVER THERE IS NOT | | INDICATION ON PLANS OF ANY REVISION. | | | | 3) NOTE: PLEASE PROVIDE SPECIFIC LIGHTING FIXTURE | | INFORMATION. PLEASE REVISE CALCULATIONS AS NEEDED. | | 13-415.2.ABC.1.1,.1.2. | | PROJECT IS UNDER THE 2004 FBC WITH 2007 REVISIONS. | | DETERMINATION OF LIGHTING ALLOWANCES MEETING CODE CAN | | NOT BE MADE WITHOUT FIXTURE INFORMATION. | | | | 4) NOTE: PLEASE SUBMIT REVISED CIRCUITING ON REVISED | | PANEL SCHEDULES. 408.4, 220, 240.4, 310.16. | | FBC 106.3.5.1.2 | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|