2009-07-24 19:49:28* DENIED REVISION **
  
 1) NOTE: FAMILY ROOM ON ORIGINAL PLANS AND REVISIONS
 INDICATING 2.1 INCLUDES THE DECRETIVE ALLOWANCES UNDER
 THE 2004 FBC. ONLY IF THIS PROJECT WAS UNDER THE 2007
 FBC WOULD THE LIGHTING ALLOWANCE BE EXCEEDED.
  
 2) NOTE: THE PREVIOUS PLANS INDICATED ROOM #241 AS
 FAMILY ROOM WITH OTHER ITEMS SUCH AS ADDITIONAL
 SWITCHES AND ADDITIONAL FIXTURES. THE ROOM 241 WAS
 REVISED FROM PLANS ON FILE HOWEVER NO REVISION HAS BEEN
 INDICATED AT THIS LOCATION. SWITCHES, FIXTURES ETC HAVE
 BEEN REMOVED.
 OTHER LOCATIONS WOULD BE HALLWAY 242 ALSO IN WHICH
 FIXTURES HAVE BEEN REMOVED HOWEVER THERE IS NOT
 INDICATION ON PLANS OF ANY REVISION.
  
 3) NOTE: PLEASE PROVIDE SPECIFIC LIGHTING FIXTURE
 INFORMATION. PLEASE REVISE CALCULATIONS AS NEEDED.
 13-415.2.ABC.1.1,.1.2.
 PROJECT IS UNDER THE 2004 FBC WITH 2007 REVISIONS.
 DETERMINATION OF LIGHTING ALLOWANCES MEETING CODE CAN
 NOT BE MADE WITHOUT FIXTURE INFORMATION.
  
 4) NOTE: PLEASE SUBMIT REVISED CIRCUITING ON REVISED
 PANEL SCHEDULES. 408.4, 220, 240.4, 310.16.
 FBC 106.3.5.1.2
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  