 APPLICATION #09020625 ELECTRICAL PLAN REVIEW
 400 S. FLAGLER DRIVE 3/27/09
 WEST PALM BEACH, FL.
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 NOTE- ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED ON THE PLAN.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS AND NRTL
 LISTING FOR ALL LUMINAIRES, BOLLARDS, POLES AND UTILITY
 PEDESTALS.
  
 3} ALL SERVICES MUST COMPLY WITH 230.95 GROUND-FAULT
 PROTECTION OF EQUIPMENT
 GROUND-FAULT PROTECTION OF EQUIPMENT SHALL BE PROVIDED
 FOR SOLIDLY GROUNDED WYE ELECTRICAL SERVICES OF MORE
 THAN 150 VOLTS TO GROUND BUT NOT EXCEEDING 600 VOLTS
 PHASE-TO-PHASE FOR EACH SERVICE DISCONNECT RATED 1000
 AMPERES OR MORE. THE GROUNDED CONDUCTOR FOR THE SOLIDLY
 GROUNDED WYE SYSTEM SHALL BE CONNECTED DIRECTLY TO
 GROUND WITHOUT INSERTING ANY RESISTOR OR IMPEDANCE
 DEVICE.
 THE RATING OF THE SERVICE DISCONNECT SHALL BE
 CONSIDERED TO BE THE RATING OF THE LARGEST FUSE THAT
 CAN BE INSTALLED OR THE HIGHEST CONTINUOUS CURRENT TRIP
 SETTING FOR WHICH THE ACTUAL OVERCURRENT DEVICE
 INSTALLED IN A CIRCUIT BREAKER IS RATED OR CAN BE
 ADJUSTED. MAKE NOTE OF THIS ARTICLE ON SHEET E-300, OR
 SHEETS THAT THE SERVICE RISER DIAGRAMS ARE ON IF MOVED
 FROM THAT SHEET.
  
 4} THE LOCATION OF THE SERVICES WILL REQUIRE A
 DISCONNECT PER 225.31 & 32. LOCATE ALL ON THE PLANS.
  
 5} PROVIDE LOAD CALCULATIONS PER ARTICLE 555.12 NEC.
 THE ???LOAD SCHEDULE??? ON SHEET E-300 DOES NOT
 INDICATE HOW THE DEMAND LOAD WAS CALCULATED.
  
 6} THE NOTE REGARDING THE 480 VOLT 3 PHASE FEEDER ON
 SHEET E-103 INCORRECTLY STATES #210G FOR THE EQUIPMENT
 GROUND. SEE 250.122 FOR SIZING.
  
 7} PER NFPA 303-2000, ARTICLE 3.3.1
 A BENCH MARK INDICATING THE ELECTRICAL DATUM PLANE OF
 THE LAND AREA SHALL BE PERMANENTLY LOCATED ON SHORE IN
 THE MARINA OR BOATYARD. INDICATE THE LOCATION ON THE
 PLANS.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO
 REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER