| APPLICATION #09020625 ELECTRICAL PLAN REVIEW |
| 400 S. FLAGLER DRIVE 3/27/09 |
| WEST PALM BEACH, FL. |
| |
| |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| NOTE- ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| OTHERWISE NOTED. |
| |
| 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| DESIGNED ON THE PLAN. |
| |
| 2} PROVIDE MANUFACTURERS SPECIFICATIONS AND NRTL |
| LISTING FOR ALL LUMINAIRES, BOLLARDS, POLES AND UTILITY |
| PEDESTALS. |
| |
| 3} ALL SERVICES MUST COMPLY WITH 230.95 GROUND-FAULT |
| PROTECTION OF EQUIPMENT |
| GROUND-FAULT PROTECTION OF EQUIPMENT SHALL BE PROVIDED |
| FOR SOLIDLY GROUNDED WYE ELECTRICAL SERVICES OF MORE |
| THAN 150 VOLTS TO GROUND BUT NOT EXCEEDING 600 VOLTS |
| PHASE-TO-PHASE FOR EACH SERVICE DISCONNECT RATED 1000 |
| AMPERES OR MORE. THE GROUNDED CONDUCTOR FOR THE SOLIDLY |
| GROUNDED WYE SYSTEM SHALL BE CONNECTED DIRECTLY TO |
| GROUND WITHOUT INSERTING ANY RESISTOR OR IMPEDANCE |
| DEVICE. |
| THE RATING OF THE SERVICE DISCONNECT SHALL BE |
| CONSIDERED TO BE THE RATING OF THE LARGEST FUSE THAT |
| CAN BE INSTALLED OR THE HIGHEST CONTINUOUS CURRENT TRIP |
| SETTING FOR WHICH THE ACTUAL OVERCURRENT DEVICE |
| INSTALLED IN A CIRCUIT BREAKER IS RATED OR CAN BE |
| ADJUSTED. MAKE NOTE OF THIS ARTICLE ON SHEET E-300, OR |
| SHEETS THAT THE SERVICE RISER DIAGRAMS ARE ON IF MOVED |
| FROM THAT SHEET. |
| |
| 4} THE LOCATION OF THE SERVICES WILL REQUIRE A |
| DISCONNECT PER 225.31 & 32. LOCATE ALL ON THE PLANS. |
| |
| 5} PROVIDE LOAD CALCULATIONS PER ARTICLE 555.12 NEC. |
| THE ???LOAD SCHEDULE??? ON SHEET E-300 DOES NOT |
| INDICATE HOW THE DEMAND LOAD WAS CALCULATED. |
| |
| 6} THE NOTE REGARDING THE 480 VOLT 3 PHASE FEEDER ON |
| SHEET E-103 INCORRECTLY STATES #210G FOR THE EQUIPMENT |
| GROUND. SEE 250.122 FOR SIZING. |
| |
| 7} PER NFPA 303-2000, ARTICLE 3.3.1 |
| A BENCH MARK INDICATING THE ELECTRICAL DATUM PLANE OF |
| THE LAND AREA SHALL BE PERMANENTLY LOCATED ON SHORE IN |
| THE MARINA OR BOATYARD. INDICATE THE LOCATION ON THE |
| PLANS. |
| |
| PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO |
| REVIEW COMMENTS IN WRITING. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |