Plan Review Notes For Permit 09020621 |
Permit Number |
09020621 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2009-09-03 11:29:09 | 400 NORTH FLAGLER DRIVE | | 09020621 | | 09020625 | | 09020628 | | 09020630 | | | | 1. ALL DOCK STANDPIPE SYSTEMS AND FIRE DEPARTMENT | | CONNECTIONS SHALL BE TESTED AT 200 PSIG FOR TWO HOURS. | | | | 2. ALL HOSE VALVES SHALL BE EQUIPPED WITH THE 2 1/2 TO | | 1 1/2 REDUCERS. | | | | 3. ALL INSPECTIONS ARE SUBJECT TO FIELD INSPECTIONS AND | | APPROVAL. | | | | 4. KNOX-BOXES SHALL BE INSTALLED AND OPERATIONAL PRIOR | | TO THE GATES BEING PLACED IN THE CLOSED POSITION. | | | | 5. ALL DOCK STANDPIPE SYSTEMS SHALL BE PROPERLY | | SECURED. | | | | 6. LOCKING CAPS ARE REQUIRED AT ALL FIRE DEPARTMENT | | CONNECTION LOCATIONS. | | | | | | APPROVED PROVISO; | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 | | |
|