Plan Review Notes
Plan Review Notes For Permit 09020621
Permit Number 09020621
Review Stop B
Sequence Number 1
Notes
Date Text
2009-04-03 16:07:46****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. G003, DECLARE EXPOSURE CLASSIFICATION FBC1603.1.4.
  
 2. DESIGN IS TO BE IN ACCORDANCE WITH FBC2004 WITH 2007
 REVISIONS/SUPPLEMENTS, FS553, FBC1604.2. PLEASE DECLARE
 GOVERNING CODE ON THE PLAN AND CONFIRM COMPLIANCE.
  
 3. PILE AND PILE CAP DESIGN AND CONSTRUCTION TO COMPLY
 WITH FBC18; PLEASE CONFIRM COMPLIANCE AND NOTE DESIGN
 CRITERIA ON THE PLAN.
  
 4. PLANS STATE THAT THE DRAWINGS ARE 100% COMPLETE BUT
 "NOT FOR CONSTUCTION;" PLEASE CLARIFY; THIS NOTE IS
 TYPICALLY USED FOR PRELIMINARY DRAWINGS IN DESIGN
 PHASE.
  
 5. THE SOIL BORING INFORMATION IN THE PLAN IS NOT
 LEGIBLE. PLEASE PROVIDE THE ORIGINAL SOILS REPORTS; SEE
 FBC1808.2.2.4, 1808.2.2.
  
 6. ENGINEER IS TO INCLUDE A TITLE BLOCK ON ALL SIGNED
 AND SEALED SHEETS WITH ALL INFORMATION REQUIRED BY
 FAC61G15-23.002. SHEETS PREPARED BY JOHN DERUGERIS, PE
 DO NOT INCLUDE A TITLE BLOCK.
  
 7. PLEASE HAVE THE ENGINEER OF RECORD FOR THE STRUCTURE
 REVIEW THE DELEGATED ENGINEERING, FAC61G15-31.
  
  
  
  