Plan Review Notes For Permit 09020609 |
Permit Number |
09020609 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-04-16 16:46:39 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | FROM PREVIOUS LIST: | | | | 5. SHUTTER CONNECTION MOUNTING TYPE NOTED ON THE | | INSTALLATION SCHEDULE IS "12"; THIS DOES NOT CORRELATE | | WITH THE ANCHOR CHARTS ON SHEET 3. THE CONNECTION TYPE | | SHOULD BE ONE INCLUDED ON THE ANCHOR CHARTS; C1 THROUGH | | C5. | | | | NOT ADDRESSED; PLEASE REVISE. SEE SHEET 3. | | | | NEW COMMENT: | | | | BASED ON THE DESIGN PRESSURE (53.24 SO MUST USE THE ROW | | FOR -63) AND SUBSTRATE (BLOCK AS STATED BY CONTRACTOR) | | EITHER 11" OR 6" SPACING REQUIRED DEPENDING ON WHICH | | SHUTTER CONNECTION MOUNTING TYPE IS USED, NOT 12". | | PLEASE REVISE. | | | | | | | | | | |
|