Plan Review Notes
Plan Review Notes For Permit 09020609
Permit Number 09020609
Review Stop B
Sequence Number 2
Notes
Date Text
2009-04-16 16:46:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 5. SHUTTER CONNECTION MOUNTING TYPE NOTED ON THE
 INSTALLATION SCHEDULE IS "12"; THIS DOES NOT CORRELATE
 WITH THE ANCHOR CHARTS ON SHEET 3. THE CONNECTION TYPE
 SHOULD BE ONE INCLUDED ON THE ANCHOR CHARTS; C1 THROUGH
 C5.
  
 NOT ADDRESSED; PLEASE REVISE. SEE SHEET 3.
  
 NEW COMMENT:
  
 BASED ON THE DESIGN PRESSURE (53.24 SO MUST USE THE ROW
 FOR -63) AND SUBSTRATE (BLOCK AS STATED BY CONTRACTOR)
 EITHER 11" OR 6" SPACING REQUIRED DEPENDING ON WHICH
 SHUTTER CONNECTION MOUNTING TYPE IS USED, NOT 12".
 PLEASE REVISE.
  
  
  
  
  