2009-03-02 13:58:46****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. ONLY TWO OPENINGS ARE SHOWN AS PROTECTED ON THE
 INSTALLATION SCHEDULE, BUT THE FLOOR PLAN SHOWS 5
 OPENINGS.
  
 2. ONE OF THE OPENINGS ON THE INSTALLATION SCHEDULE
 DOES NOT INCLUDE THE OPENING SIZE.
  
 3. THE OPENINGS ON THE FLOOR PLAN SHOULD BE NUMBERED,
 TO CORRELATE WITH THE OPENINGS ON THE INSTALLATION
 SCHEDULE.
  
 4. THE FASTENER SPECIFIED, ELCO TAPCON, IS NOT AN
 OPTION IN THE PRODUCT APPROVAL SUBMITTED, SEE SHEET 3.
 ENGINEERING WOULD BE REQUIRED TO USE FASTENERS OTHER
 THAN THOSE TESTED/ENGINEERED IN THE PRODUCT APPROVAL.
  
 5. SHUTTER CONNECTION MOUNTING TYPE NOTED ON THE
 INSTALLATION SCHEDULE IS "12"; THIS DOES NOT CORRELATE
 WITH THE ANCHOR CHARTS ON SHEET 3. THE CONNECTION TYPE
 SHOULD BE ONE INCLUDED ON THE ANCHOR CHARTS; C1 THROUGH
 C5.
  
 6. NOTE THAT ONLY TWO FASTENER TYPES ALLOWED FOR 2"
 EDGE DISTANCE, SEE SHEET 3 OF THE PRODUCT APPROVAL.
  
  
  