Plan Review Notes
Plan Review Notes For Permit 09020598
Permit Number 09020598
Review Stop P
Sequence Number 1
Notes
Date Text
2009-03-12 15:37:10DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 EXISTING BUILDING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. IF THE DESIGN PROFESSIONAL
 IS AN ARCHITECT LEGALLY REGISTERED UNDER THE LAWS O
 THIS STATE REGULATING THE PRACTICE OF ARCHITECTURE AS
 PROVIDED FOR IN CHAPTER 481 FLORIDA STATUTES, THEN HE
 OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE
 AND DATE TO SAID DRAWINGS, AS REQUIRED BY FLORIDA
 STATUTES. SECTION 106.1.
  
 2. SHT P1.01 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AS IT INDICATES AN EXISTING VTR,
 WHERE AS THE FLOOR PLAN INDICATES A NEW VTR. PLEASE
 CORRELATE. SECTION 106.1.1 -- HAND WRITTEN CHANGES TO A
 SIGNED, SEALED, DATED SET OF PLANS ARE NOT APPROVED.
 SECTION 106.1.3.
  
 5. SHT P1.01 WATER ISOMETRIC RISER DIAGRAM SHOWS AIR
 CHAMBERS AT THE SINK. AIR CHAMBERS ARE NOT APPROVED.
 PLEASE DELETE. SECTION 604.9 & PDI-WH 201. SECOND NOTE
 ONE INDICATES WATER HAMMER ARRESTORS ON THE HOT & COLD
 LINES BUT ONLY THE HOT LINE AT THE DISH WASHER IS
 SHOWING A WATER HAMMER ARRESTOR. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  