2009-03-12 15:37:10 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| FBC-2004 EXISTING BUILDING |
| FBC-2004 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. ALL ARCHITECTURAL SHEETS. IF THE DESIGN PROFESSIONAL |
| IS AN ARCHITECT LEGALLY REGISTERED UNDER THE LAWS O |
| THIS STATE REGULATING THE PRACTICE OF ARCHITECTURE AS |
| PROVIDED FOR IN CHAPTER 481 FLORIDA STATUTES, THEN HE |
| OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE |
| AND DATE TO SAID DRAWINGS, AS REQUIRED BY FLORIDA |
| STATUTES. SECTION 106.1. |
| |
| 2. SHT P1.01 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN AS IT INDICATES AN EXISTING VTR, |
| WHERE AS THE FLOOR PLAN INDICATES A NEW VTR. PLEASE |
| CORRELATE. SECTION 106.1.1 -- HAND WRITTEN CHANGES TO A |
| SIGNED, SEALED, DATED SET OF PLANS ARE NOT APPROVED. |
| SECTION 106.1.3. |
| |
| 5. SHT P1.01 WATER ISOMETRIC RISER DIAGRAM SHOWS AIR |
| CHAMBERS AT THE SINK. AIR CHAMBERS ARE NOT APPROVED. |
| PLEASE DELETE. SECTION 604.9 & PDI-WH 201. SECOND NOTE |
| ONE INDICATES WATER HAMMER ARRESTORS ON THE HOT & COLD |
| LINES BUT ONLY THE HOT LINE AT THE DISH WASHER IS |
| SHOWING A WATER HAMMER ARRESTOR. PLEASE CORRELATE. |
| SECTION 106.1.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |