2009-02-27 10:19:422004 FBC W/2007 REVISIONS
 RE-ROOF
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 TAMKO MODIFIED SYSTEM NOA 03-0501.02 ARE EXPIRED.
 SUBMIT CURRENT PRODUCT APPROVALS.
  
 3) SPECIFY THE FASTENING OPTION AND DESIGN PRESSURE FOR
 THE SYSTEM THAT WILL BE INSTALLED. CIRCLE THE
 APPROPRIATE ONE ON THE NOA.
  
 4) THE FL COVERSHEET FOR THE MODIFIED SYSTEM FL 206 IS
 FOR A LIBERTY BASE SHEET AND NOT THE ONE FOR THE
 MODIFIED SYSTEM ON THE NOA THAT WAS SUBMITTED. PLEASE
 SUBMIT MATCHING COVERSHEET AND PRODUCT APPROVALS.
  
 5) THE FL COVERSHEET FOR THE ASPHALT SHINGLES FL 183 IS
 NOT THE ONE FOR TIMBERLINE PRESTIQUE 40 SHINGLES. SEE
 FL10124. SUBMIT MATCHING COVERSHEET AND PRODUCT
 APPROVALS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714