2009-05-20 16:00:26 | REVISION DENIED |
| REFERENCE: |
| FBC-2004 RESIDENTIAL |
| FBC-2004 FUEL GAS |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. - THE ISOMETRIC INDICATES 1 FT FROM THE |
| METER TO THE HORIZONTAL UNDERGROUND P.E. PIPE. THE |
| MINIMUM BURIAL DEPTH FOR UNDERGROUND PIPE IS 1 FT. |
| PLEASE INDICATE THE MEASUREMENT FROM THE GROUND TO THE |
| OUTLET OF THE METER. SECTION G2415.9, (404.9). |
| |
| 2. THE ISOMETRIC SHOWS A 3/4" TO 1/2" REDUCER AT GROUND |
| LEVEL. THE PIPING SHALL BE FULL SIZE THRU THE SHUT OFF |
| VALVE. TABLE 402.4(20). |
| |
| 3. THE ISOMETRIC SHOW THE PIPING TO BE 3/4". PER TABLE |
| 402.4(20) FOR 20 FT THE MINIMUM PIPE SIZE FOR 294,000 |
| BTU SHALL BE 1". |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |