2009-04-15 10:52:38DENIED
 REFERENCE;
 FBC-2004 FUEL GAS/RESIDENTIAL
  
 1. CONFLICTING INFORMATION SUBMITTED. ON THE RISER
 DIAGRAM SUBMITTED FOR THE GAS PERMIT THERE IS INDICATED
 AN EXISTING GAS METER, BUT ON THE ELECTRICAL SHEET WITH
 THE LOAD CALCULATION THERE IS INDICATED A NEW GAS
 METER. PLEASE CLARIFY. IF THERE IS AN EXISTING GAS
 METER AND EXISTING GAS PIPING THEN THE TOTAL BTU LOAD
 OF THE EXISTING GAS PIPING AND DISTANCE TO THE MOST
 REMOTE OUTLET IN THE SYSTEM SHALL BE INDICATED ON THE
 PLANS. SECTIONS 402.4.1 OR G2413.4.1.
  
 2. PIPE MATERIAL IS INDICATED AS GALVANIZED. AS
 GALVANIZED PIPE IS NOT APPROVED UNDERGROUND PLEASE
 INDICATE IF THE PIPING WILL BE ABOVE THE GROUND. IF
 UNDERGROUND THEN THE PIPING SHALL BE FACTORY WRAPPED.
 SECTIONS 404.8, 404.8.2. & G2415.8, G2415.8.2.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). -- BTU LOAD IS INDICATED AS 250,000 BTU BUT
 THE MANUF. INFORMATION INDICATES THE BTU LOAD AS
 294,000. PLEASE CORRELATE. SECTIONS 402.2 & G24.13.2.
  
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -- TABLE 402.4(24)
 SUBMITTED IS INDICATED AS 11.0 INCH WC BUT THE
 ISOMETRIC SUBMITTED SHOWS A 2ND STAGE REGULATOR. PLEASE
 CLARIFY. ALSO THE TABLE SUBMITTED IS FOR LP GAS AND THE
 PLANS INDICATE NATURAL GAS. PLEASE CLARIFY.
  
 5. A LISTED SHUT OFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTIONS 409.4
 & G2420.4.
  
 6. SUBMIT THE MANUF. SPECIFICATIONS FOR THE 2ND STAGE
 REGULATOR. REGULATOR SHALL INDICATE A LISTING, SHOW
 MODEL NUMBER AND SHOW OUTLET LOAD CAPACITY. SECTIONS
 410.2 & G2421.2.
  
 ****INFORMATIONAL**** THE LICENSE NUMBER 24451 IS FOR
 SALES OF GAS GENERATORS ONLY. PLEASE INDICATE THE
 LICENSE REQUIRED FOR GAS PIPE INSTALLATION, 24513 ON
 FUTURE APPLICATIONS FOR GAS PERMITS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  