Plan Review Notes
Plan Review Notes For Permit 09020579
Permit Number 09020579
Review Stop P
Sequence Number 1
Notes
Date Text
2009-04-14 11:52:02DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. PLANS SHALL INDICATE THE LOCATION OF THE WORK IN THE
 TITLE BLOCK. THE ADDRESS INDICATED ON THE APPLICATION
 AND IN THE CITY ADDRESSING SYSTEM IS 425 BELVEDERE
 ROAD. SECTION 106.1.1
  
 2. SUBMIT A SITE PLAN INDICATING THE LOCATION OF THE
 SEWER CONNECTION, THE WATER METER, THE BACKFLOW, THE
 SEWER PIPING & THE WATER SERVICE LINE. SECTIONS 106.1.2
 (MORE INFORMATION REQUIRED), 603, 701, 708, ETC.
  
 3. PER TABLE 403.1 A SERVICE SINK IS REQUIRED IN ALL
 STORAGE OCCUPANCIES. PLEASE INDICATE THE LOCATION OF
 THE REQUIRED SINK.
  
 4. SHOW COMPLIANCE FOR THE FOLLOWING:
  
 ___W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.4 GRAB BARS (MINIMUM 36" REQUIRED BEHIND THE
 W/C - 30" SHOWN)
  
 ___LAV:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
  
 ___D/F:
 A. 11-4.15.5 CLEAR FLOOR SPACE (FORWARD APPROACH REQD)
 B. 11-4.1.3(10(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 5. SHT 4 OF 4 SANITARY RISER DIAGRAM, A TWO WAY
 CLEANOUT SHALL BE USED NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER, OR A SEPARATE
 CLEANOUT FOR THE SEWER IS REQUIRED. SECTION 708.3.2.
  
 6. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED PER
 SECTION 106.3.5.1.3. INDICATE ALL PIPE SIZES, VALVES,
 ETC.
  
 7. HOT WATER IS REQUIRED FOR THE SERVICE SINK PER
 SECTION 607.1. PLEASE SHOW ON THE FLOOR PLAN AND THE
 WATER ISOMETRIC RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved