Plan Review Notes
Plan Review Notes For Permit 09020579
Permit Number 09020579
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-04-14 10:01:40*****UNSAT*****
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2. DISPLAY/SHOW THE NUMERICAL ADDRESS OF THE BUILDING
 ON THE APPROPIATE EXTERIOR ELEVATION VISIBLE FROM
 BELVEDERE ROAD. AS PER WEST PALM BEACH CODE, THE
 ADDRESS NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND
 NO LESS THAN 1" IN WIDTH/STROKE. IN THE EVENT THAT THE
 VISIBILITY OF THE ADDRESS IS NOT PLAINLY VISIBLE FROM
 THE ROADWAY, A MARKEE AND/OR SIGN POST WITH THE ADDRESS
 WILL BE REQUIRED IN ADDITION TO THE ADDRESS ON THE
 BUILDING.
  
 3. LANDSCAPING AND THE LIKE SUCH OPERATIONS SHALL NOT
 OBSTRUCT A FIRE HYDRANT OR FIRE PROTECTION APPLIANCE
 AND HINDER OR PREVENT ITS IMMEDIATE USE BY THE FIRE
 PERSONNEL. SUCH FIRE HYDRANT OR FIRE PROTECTION
 APPLIANCE SHALL BE MAINTAINED READILY VISIBLE AT ALL
 TIMES.
  
 4. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER LOCATED INSIDE THE STRUCTURE.
  
 5. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 6. BASED ON THE ASSUMPTION THAT THIS STRUCTURE IS A
 STORAGE OCCUPANCY, CLASSIFY THE MATERIALS TO BE STORED
 AS LOW HAZARD, ORDINARY HAZARD, OR HIGH HAZARD.
  
 7. ON SHEET A04, A SMOKE DETECTOR (SD) IS SHOWN IN THE
 ELECTRICAL FLOOR PLAN. IS THIS DEVICE A SMOKE DETECTOR
 OR A SMOKE ALARM (SA)? PLEASE BE ADVISED THAT A SMOKE
 DETECTOR IS TIED TO THE BUILDING'S FIRE ALARM SYSTEM
 WHEREAS A SMOKE DETECTOR ALERTS THE OCCUPANT(S) ONLY
 AND IS NOT TIED INTO A FIRE ALARM SYSTEM.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHER E EACH COMMENT WAS ADDRESSED.
  