Date |
Text |
2009-04-14 10:01:40 | *****UNSAT***** |
| |
| 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK |
| OF EACH SUBMITTED PLAN SHEET. |
| |
| 2. DISPLAY/SHOW THE NUMERICAL ADDRESS OF THE BUILDING |
| ON THE APPROPIATE EXTERIOR ELEVATION VISIBLE FROM |
| BELVEDERE ROAD. AS PER WEST PALM BEACH CODE, THE |
| ADDRESS NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND |
| NO LESS THAN 1" IN WIDTH/STROKE. IN THE EVENT THAT THE |
| VISIBILITY OF THE ADDRESS IS NOT PLAINLY VISIBLE FROM |
| THE ROADWAY, A MARKEE AND/OR SIGN POST WITH THE ADDRESS |
| WILL BE REQUIRED IN ADDITION TO THE ADDRESS ON THE |
| BUILDING. |
| |
| 3. LANDSCAPING AND THE LIKE SUCH OPERATIONS SHALL NOT |
| OBSTRUCT A FIRE HYDRANT OR FIRE PROTECTION APPLIANCE |
| AND HINDER OR PREVENT ITS IMMEDIATE USE BY THE FIRE |
| PERSONNEL. SUCH FIRE HYDRANT OR FIRE PROTECTION |
| APPLIANCE SHALL BE MAINTAINED READILY VISIBLE AT ALL |
| TIMES. |
| |
| 4. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE |
| EXTINGUISHER LOCATED INSIDE THE STRUCTURE. |
| |
| 5. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE |
| REFERENCED. |
| |
| 6. BASED ON THE ASSUMPTION THAT THIS STRUCTURE IS A |
| STORAGE OCCUPANCY, CLASSIFY THE MATERIALS TO BE STORED |
| AS LOW HAZARD, ORDINARY HAZARD, OR HIGH HAZARD. |
| |
| 7. ON SHEET A04, A SMOKE DETECTOR (SD) IS SHOWN IN THE |
| ELECTRICAL FLOOR PLAN. IS THIS DEVICE A SMOKE DETECTOR |
| OR A SMOKE ALARM (SA)? PLEASE BE ADVISED THAT A SMOKE |
| DETECTOR IS TIED TO THE BUILDING'S FIRE ALARM SYSTEM |
| WHEREAS A SMOKE DETECTOR ALERTS THE OCCUPANT(S) ONLY |
| AND IS NOT TIED INTO A FIRE ALARM SYSTEM. |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHER E EACH COMMENT WAS ADDRESSED. |
| |
| CAPT MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |