Date |
Text |
2009-03-26 16:49:42 | ** DENIED REVIEW ** |
| |
| 1) NOTE: PLEASE SEE THE ADDRESS LOCATION ON PLANS NEEDS |
| TO CORRELATE WITH THE LOCATION AS APPLIED. THE PLANS |
| CALL FOR AVON RD. HOWEVER ACTUAL LOCATION IS 425 |
| BELVEDERE RD. |
| |
| 2) NOTE: RISER INDICATES AN EQUIPMENT GROUNDING |
| CONDUCTOR FROM METER TO MAIN. THIS IS NOT PERMITTED PER |
| 250.6,250.24 |
| |
| 3) NOTE: THE SUBMITTED LOAD CALCULATIONS DO NOT MEET |
| THE MINIMUM NEC 220 REQUIREMENTS. PLEASE SEE NEC |
| 220.12,220.14,220.44, 220.42 ETC |
| PLEASE ALSO BE SURE TO SEE 215.3,230.42 ETC FOR ALL |
| CONTINUOUS LOADS WHICH ARE REQUIRED TO BE SHOWN AT |
| 125%. |
| |
| 3) NOTE: PLEASE BE SURE TO COORDINATE THE PANEL |
| SCHEDULE AND LOAD CALCULATIONS. SOME EXAMPLES OF ITEMS |
| WHICH DO NOT COORDINATE IS POOL PUMP, WATER COOLER/ |
| BOTH DO THESE ARE NOT ON PANEL SCHEDULES. SOME ITEMS ON |
| SCHEDULE NOT IN LOAD CALCULATIONS ARE SPRINKLER PUMP. |
| 408.4, 220. |
| |
| 4) NOTE: PLEASE SEE SOME LIGHTS ON PLANS NOT ON ANY |
| CONTROL OR CIRCUIT. THIS WAS REDLINED ON ONE COPY. |
| PLEASE SEE 408.4, 310.16, 220 ETC FOR MINIMUMS. |
| |
| 5) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.4 FOR REQUIRED |
| EXTERIOR LIGHTING CONTROLS. MAY NOT USE STANDARD SINGLE |
| POLE SWITCHES. |
| |
| 6) NOTE: PLEASE PROVIDE PRESCRIPTIVE SPACE PERFORMANCE |
| LEVELS PER 13-415.2.ABC.1.1, .1.2. PLEASE SEE |
| 13-415.2.B.2 FOR EXTERIOR OF BUILDING PERFORMANCE |
| LEVELS. |
| |
| 7) NOTE: PLEASE PROVIDE INFORMATION ON WHAT THE *E* ON |
| THE PLANS IS. THIS IS LOCATED ON THE SHED PLANS. IS |
| THIS AN EXIT SIGN? |
| IF SO THE SYMBOL LEGEND DOES NOT INDICATE THIS SYMBOL |
| AND THERE IS NOT CIRCUIT SHOWN. PLEASE SEE 700.12F FOR |
| CIRCUITING IF INDEED AN EXIT SIGN OR SOME SORT. |
| |
| 8) NOTE: PLEASE PROVIDE AIC RATINGS FOR ALL EQUIPMENT |
| PER 110.9. ALL SERVICE EQUIPMENT AND BREAKERS SHALL BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| |
| 9) NOTE: PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION |
| PER CHAPTER 3 OF THE FBC. |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |