| APPLICATION #09020560 ELECTRICAL PLAN REVIEW |
| 836 ALMERIA ROAD #836-840 3/5/09 |
| WEST PALM BEACH, FL. |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| THIS COMMENT WAS PART OF THE PREVIOUS REVIEW |
| 1} SEE 230.2 NUMBER OF SERVICES |
| A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED |
| BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A) |
| THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2 |
| ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND |
| LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED |
| TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER |
| AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING |
| ONE SERVICE*** FROM THE PARTIAL RISER SUBMITTED IT |
| CANNOT BE DETERMINED IF COMPLIANCE WITH THIS ARTICLE IS |
| MET. |
| |
| NEW COMMENTS GENERATED BY THE RISER CHANGE. |
| |
| 2} THE CONDUCTORS FROM THE DISCONNECT LOCATION NOW |
| SHOWN ARE RUNNING OVERHEAD AND POSSIBLY PANEL "B" IS |
| BEING FEED THROUGH BUILDING "A" IN VIOLATION OF 230..3 |
| NEC |
| |
| 3} THE FEED FROM THE DICONNECTS TO THE PANEL MUST |
| CONTAIN AN EQUIPMENT GROUND PER 250.122. NEC |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |