 APPLICATION #09020560 ELECTRICAL PLAN REVIEW
 836 ALMERIA ROAD #836-840 3/5/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THIS COMMENT WAS PART OF THE PREVIOUS REVIEW
 1} SEE 230.2 NUMBER OF SERVICES
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE*** FROM THE PARTIAL RISER SUBMITTED IT
 CANNOT BE DETERMINED IF COMPLIANCE WITH THIS ARTICLE IS
 MET.
  
 NEW COMMENTS GENERATED BY THE RISER CHANGE.
  
 2} THE CONDUCTORS FROM THE DISCONNECT LOCATION NOW
 SHOWN ARE RUNNING OVERHEAD AND POSSIBLY PANEL "B" IS
 BEING FEED THROUGH BUILDING "A" IN VIOLATION OF 230..3
 NEC
  
 3} THE FEED FROM THE DICONNECTS TO THE PANEL MUST
 CONTAIN AN EQUIPMENT GROUND PER 250.122. NEC
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  